7 - 29 7 - 29
MELSEC-Q
7 ONLINE MODULE CHANGE
7.3.6 When user range setting is used and initial setting was made with sequence program
(other system is unavailable)
(1) Conversion
disable
(a) Set Conversion enable/disable setting (buffer memory address 0: Un\G0)
for all channel conversion disable and turn the operating condition setting
request (Y9) from OFF to ON to stop conversion.
After confirming that conversion has stopped with the Conversion
Completion Flag (buffer memory address 10: Un\G10), turn off Operating
Condition Setting Request (Y9).