App. - 14 App. - 14
MELSEC-Q
APPENDIX
Appendix 3.4 OGSTOR
Restores the offset/gain values of the user range setting stored in the CPU to the
Q64RD/Q64RD-G.
Usable devices
Internal device
(System, user)
Link direct device
J \
Constant
Set data
Bit Word
File
register
Bit Word
Intelligent
function
module
device
U \G
Index
register
Z
K, H
S
Other
(S) —
—
— — —
(D)
—
— — —
Command
G.OGSTOR
Command
GP.OGSTOR
Un
(S)
(D)
Un
(S)
(D)
[Instruction
symbol]
[Execution
condition]
G.OGSTOR
GP.OGSTOR
Set data
Device
Description
Setting range
Data type
Un
Start I/O number of the module
0 to FE
H
Binary 16 bits
(S)
1
Start number of the device in which control data is stored.
Within the range of the
specified device
Device name
(D)
Device that is turned ON 1 scan on completion of dedicated
instruction processing.
(D) + 1 also turns ON at an abnormal completion.
Within the range of the
specified device
Bit
1 When executing the G.OGLOAD instruction, specify the device designated in (S).
Do not change the data read with the G.OGLOAD instruction.
If it is changed, normal operation cannot be guaranteed.
Control data
1
(1/4)
Device Item
Set
data
Setting
range
Set by
(S) System
area
— —
—
(S) + 1
Completion status
Stores the status when the
instruction is complete.
0 : Normal completion
Other than 0: Abnormal
completion
— System
(S) + 2
(S) + 3
System area
—
—
—
(S) + 4 3-wire CH1 Factory default offset value
—
—
System
(S) + 5 3-wire CH1 Factory default offset value
—
—
System
(S) + 6 3-wire CH1 Factory default gain value
—
—
System
(S) + 7 3-wire CH1 Factory default gain value
—
—
System
(S) + 8 3-wire CH1 User range settings offset value
—
—
System
(S) + 9 3-wire CH1 User range settings offset value
—
—
System
(S) + 10 3-wire CH1 User range settings gain value
—
—
System
Q64RD
(S) + 11 3-wire CH1 User range settings gain value
—
—
System
1 Setting is not necessary. If setting is made, the offset/gain values will not be read properly.
Summary of Contents for q64rd