7 ONLINE MODULE CHANGE
(e) Monitor the measured temperature values (16 bits) (buffer memory
addresses 11 to 14: Un\G11 to 14) or measured temperature values (32
bits) (buffer memory addresses 54 to 61: Un\G54 to 61) to check that
proper conversion has been made.
(5) Resumption of control
(a) After choosing [Diagnosis] - [Online module change] on GX Developer to
redisplay the "Online module change" screen, click the [Execution] button to
resume control. The FROM/TO instruction for the module resumes.
(b) The "Online module change completed" screen appears.