12.1 Transient Transmission Function
12.1.2 Routing function
(4) Routing parameter setting
(a) Setting screen
Up to 64 "Target Network No." can be set on the "Routing Parameter Setting"
screen of the CC IE Control utility.
The same target network number cannot be set more than one (multiple). For this
reason, the own station may become a request source, and up to 64 types of
"Target Network No." can be used to access to other stations through the own
station.
Setting item
Description
Valid setting range
Target network No.
Set a network No. of another network.
1 to 239
Relay network No.
Set a network No. of own network.
1 to 239
Relay station No.
Set a station No. of the relay station in
own network.
1 to 120
Maximum size of transient
transmission when
relaying other networks.
Set the maximum transmission size
of transient transmission.
960 words
480 words