13
ERROR CODES
9
DEVICE MONIT
O
R
UT
IL
ITY
10
MELS
EC D
A
TA
LI
N
K
LI
BRAR
Y
11
PROGRAMMING
12
AP
PLI
C
A
T
IO
N
FUNCT
IONS
13
E
R
ROR COD
E
S
14
TROU
BL
E
S
H
O
O
T
ING
A
APPE
NDICES
I
INDEX
13.1 List of Error Messages in CC IE Control Utility
13.1.2 Error messages displayed on the setting screen
13
- 4
(2) Network range assignment screen
Error message
Corrective action
The I/O master station set/erase station No. is not selected.
Please select the I/O master station set/erase station No.
Select one station number only, and press the I/O master
station specification button.
Two or more stations are selected for the I/O master station
set/erase station No.
Please select 1 station for the I/O master station set/erase
station No.
Select one station number only, and press the I/O master
station specification button.
The reserved station set/erase station No. is not selected.
Please select the reserved station set/erase station No.
Select the station number, and press the Reserve station
specification button.
The specified station No. is set as the I/O master station.
Please erase the I/O master station and set the reserved
station.
Erase the I/O master station and set the reserved station.
The number of points setting value is outside the range.
Please input the value within the range XX-YY.
Set the value for the points within the range of XX to YY.
The start device No. setting value is outside the range.
Please input the value within the range XX-YY.
Set the value for the start device number within the range of
XX to YY.
The end device No. setting value is outside the range.
Please input the number within the range XX-YY.
Set the value for the end device number within the range of
XX to YY.
The LB/LW settings 1 are overlapping.
Please set them so that they do not overlap.
Set the LB/LW settings 1 not to overlap.
The LB/LW settings 2 are overlapping.
Please set them so that they do not overlap.
Set the LB/LW settings 2 not to overlap.
The L station to M station setting in LX/LY settings 1 are
overlapping.
Please set them so that they do not overlap.
Set the L station to M station setting in LX/LY settings 1 not to
overlap.
The M station to L station setting in LX/LY settings 1 are
overlapping.
Please set them so that they do not overlap.
Set the M station to L station setting in LX/LY settings 1 not to
overlap.
The L station to M station setting in LX/LY settings 2 are
overlapping.
Please set them so that they do not overlap.
Set the L station to M station setting in LX/LY settings 2 not to
overlap.
The M station to L station setting in LX/LY settings 2 are
overlapping.
Please set them so that they do not overlap.
Set the M station to L station setting in LX/LY settings 2 not to
overlap.
Master station XX is not set.
Please set the master station.
Set the I/O master station XX.
Can not set all stations as "Reserved station".
Please change any of the station to other than reserved
station.
Change one or more specified reserved station that is set as
a network range assignment, to stations other than reserved
stations.
The number of LB points per station exceeds 16384 points.
Please set the settings so that the number of LB points per
station does not exceed 16384 points.
Set the value for the LB points not to exceed 16384 points.
The number of LW points per station exceeds 16384 points.
Please set the settings so that the number of LW points per
station does not exceed 16384 points.
Set the value for the LW points not to exceed 16384 points.
The monitoring time setting value is outside the range.
Please input the value within the range 5-2000.
Set the value for the monitoring time within the range of 5 to
2000.