14.3 When CC-Link IE Controller Network Board did not Operate Normally
14.3.2 Checking on Event Viewer screen
14
- 11
*1: The event 256(0100
H
) may be registered to the log as an error when the versions of the driver and
the application that are installed are different. Install the software package (SW1DNC-MNETG-B)
whose version is the same as that of the installed driver.
291(0123
H
)
Failed to map the shared memory area.
• Remove another I/F board.
• Change the I/O port address of another I/F board on the
BIOS setting screen.
294(0126
H
)
The I/O port of the I/F board overlaps with
that of another hardware.
• Remove another I/F board.
• Change the I/O port address of another I/F board on the
BIOS setting screen.
295(0127
H
)
Board WDT error occurred.
The board may be a failure.
Please consult your local Mitsubishi representative.
296(0128
H
)
Clock stop error occurred in the board.
The board may be a failure.
Please consult your local Mitsubishi representative.
297(0129
H
)
Target abort error occurred in the board.
The board may be a failure.
Please consult your local Mitsubishi representative.
304(0130
H
)
Data parity error occurred in the board.
The board may be a failure.
Please consult your local Mitsubishi representative.
305(0131
H
)
Entering sleep mode or hibernation mode,
or fast startup is detected.
The board is not operated normally
because the sleep mode, hibernation
mode, and fast startup is not supported by
the board.
Change the power option not to enter the sleep mode, hiber-
nation mode, or enabling fast startup and restart the personal
computer.
307(0133
H
)
Link refresh error had occurred.
• Reset the board.
• The memory may be insufficient.
Please close other applications running.
• Terminate the program and restart the personal computer.
• Check the free space of the memory.
• Check the board installation status.
•
The personal computer is faulty when other personal
computers normally operate. Repair or replace the faulty
personal computer.
• When the same error occurs in another personal
computer, replace the CC-Link IE Controller Network
board.
• Consult your local Mitsubishi service center or representative.
512(0200
H
)
PCI bus error occurred.
• When the same error occurs in another personal
computer, replace the CC-Link IE Controller Network
board.
• The personal computer is faulty when other personal
computers normally operate. Repair or replace the faulty
personal computer.
539(021B
H
)
The breakdown of hardware was detected.
• Change the power option not to enter the sleep mode,
hibernation mode, or enabling fast startup and restart the
personal computer.
• Restart the personal computer.
If any of the above actions do not solve the error, the board
may be a failure.
Please consult your local Mitsubishi representative.
Event ID.
Error message
Corrective action