236
6 OPTIONS AND PERIPHERAL EQUIPMENT
6.17 MR-J3-D05 safety logic unit
Functions and configuration
Outline
The MR-J3-D05 has two systems of output for the SS1 function (delay time) and the STO function each.
Specifications
*1 An inrush current of approximately 1.5 A flows momentarily at power-on. Take the inrush current into account when selecting a power
supply.
*2 The service life lasts until the power is turned on 100,000 times.
*3 A number and axis name are put in the _ portion of a signal name.
*4 For details of test pulse input, contact your local sales office.
Safety logic unit model
MR-J3-D05
Control circuit
power supply
Voltage
DC 24 V
Permissible voltage fluctuation
24 V DC ±10 %
Required current capacity [A]
0.5
Supported system
2 systems (A-axis, B-axis independent)
Shut-off input
4-point (2 points x 2 systems) SDI_: Source/sink supported
Shut-off release input
2-point (1 point x 2 systems) SRES_: Source/sink supported
Feedback input
2-point (1 point x 2 systems) TOF_: Source supported
Input method
Photocoupler insulation, 24 V DC (externally supplied), 5.4 k
Ω
internal resistance
Shut-off output
8-point (4 points x 2 systems) STO_: Source supported
8-point (4 points x 2 systems) SDO_: Source/sink supported
Output method
Photocoupler insulation, open-collector type
Permissible current: 40 mA or less per point, inrush current: 100 mA or less per point
Delay setting time
A-axis: Select from 0 s,1.4 s, 2.8 s, 5.6 s, 9.8 s, and 30.8 s.
B-axis: Select from 0 s,1.4 s, 2.8 s, 9.8 s, and 30.8 s.
Accuracy: ±2 %
Safety sub-function
STO, SS1 (IEC/EN 61800-5-2)
EMG STOP, EMG OFF (IEC/EN 60204-1)
Safety
performance
Satisfied standards
ISO 13849-1: 2015 Category 3 PL d, IEC 61508 SIL 2, IEC 62061 SIL CL 2, IEC 61800-5-2
Response performance (when
the delay setting time is 0 s)
10 ms or less (STO input off
→
shut-off output off)
Mean time to dangerous failure
(MTTFd)
MTTFd
≥
100 [years] (516a)
Diagnostic coverage (DC)
DC = Medium, 93.1 [%]
Probability of dangerous Failure
per Hour (PFH)
PFH = 4.75 × 10
-9
[1/h]
Satisfied
standards
CE marking
LVD: EN 61800-5-1
EMC: EN 61800-3
MD: EN ISO 13849-1: 2015, EN 61800-5-2, EN 62061
Structure
Natural cooling, open (IP rating: IP00)
Environment
Ambient temperature
Operation: 0
˚
C to 55
˚
C (non-freezing), Storage: -20
˚
C to 65
˚
C (non-freezing)
Ambient humidity
Operation: 5 %RH to 90 %RH (non-condensing), Storage: 5 %RH to 90 %RH (non-condensing)
Ambience
Indoors (no direct sunlight); no corrosive gas, inflammable gas, oil mist or dust
Altitude
1000 m or less
Vibration resistance
5.9 m/s
2
, 10 Hz to 55 Hz (in each of the X, Y, and Z directions)
Mass [kg]
0.2 (including CN9 and CN10 connectors)
Summary of Contents for Melservo-J5 MR-J5 Series
Page 2: ......
Page 441: ...12 USING A FULLY CLOSED LOOP SYSTEM 12 7 Absolute position detection system 439 12 MEMO ...
Page 445: ......