226
6 OPTIONS AND PERIPHERAL EQUIPMENT
6.15 Earth-leakage current breaker
Selection example
This section shows examples of selecting an earth-leakage current breaker under the following conditions.
MR-J5-_G_ or MR-J5-_A_
Use an earth-leakage current breaker designed for suppressing harmonics/surges.
Find each term of formula (6.1) from the diagram.
Ign = 0 (not used)
Iga = 0.1 [mA]
Igm = 0.1 [mA]
Insert these values in formula (6.1).
Ig
≥
10 • {0.1 + 0 + 0.1 + 1 • (0.1 + 0.1)}
Ig
≥
4 [mA]
According to the result of calculation, use an earth-leakage current breaker having the rated sensitivity current (Ig) of 4.0 mA
or more.
Use an earth-leakage current breaker having Ig of 15 mA for the NV-SP/SW/CP/CW/HW series.
HK-KT43
2 mm
2
× 5 m
2 mm
2
× 5 m
NV
Ig1
Iga
Ig2
Igm
MR-J5-40G
M
Servo amplifier
Servo motor
5
1000
Ig1 = 20 •
= 0.1 [mA]
5
1000
Ig2 = 20 •
= 0.1 [mA]
Summary of Contents for Melservo-J5 MR-J5 Series
Page 2: ......
Page 441: ...12 USING A FULLY CLOSED LOOP SYSTEM 12 7 Absolute position detection system 439 12 MEMO ...
Page 445: ......