![Mitsubishi Electric MELSEC Q80BD-J71GF11-T2 User Manual Download Page 85](http://html.mh-extra.com/html/mitsubishi-electric/melsec-q80bd-j71gf11-t2/melsec-q80bd-j71gf11-t2_user-manual_238449085.webp)
7 OVERVIEW OF CC IE FIELD UTILITY
7.1 Overview
83
7
7
OVERVIEW OF CC IE FIELD UTILITY
CC IE Field Utility is software to display settings and status of the CC-Link IE Field Network board.
For installing and uninstalling the CC IE Field utility, refer to the following section.
Page 80 INSTALLING AND UNINSTALLING SOFTWARE PACKAGES
7.1
Overview
Use CC IE Field Utility to perform the following functions.
Item
Description
Menu
Reference
Test before
wiring
Bus I/F test
Check the hardware of the Bus I/F function of the CC-Link IE
Field Network board.
[Diagnostics]
[Board
Diagnostics]
Memory test
Check the memory of the CC-Link IE Field Network board.
Hardware test
Check the hardware in the CC-Link IE Field Network board.
Self-loopback test
Test the hardware of the CC-Link IE Field Network board
alone, including the send/receive circuit of the transmission
system and cables.
Setting
Parameter Setting
Set the network parameters.
[View]
[Network
Parameter]
[Online]
[Read from
Board]/[Write to Board]
Page 113 Writing/
Reading Parameters to/
from Board
Channel number
setting
Set channel numbers of the CC-Link IE Field Network board.
[Online]
[Channel No.
Setting]
Page 112 Setting Board
Channel Numbers
Test after
wiring
Loop test
Check the network circuit status and parameter setting status
of each station.
[Diagnostics]
[Board
Diagnostics]
Cable test
Check disconnections and incomplete connections of Ethernet
cables.
[Diagnostics]
[CC IE
Field Diagnostics]
Communication test
Check whether the communication path for transient
transmission from the own station to the target station is
correct.
Monitor/
Debug
Device monitor
Start Device Monitor Utility and monitor devices.
[Online]
[Device
Monitor Utility]
CC-Link IE Field
Network diagnostics
Check error locations, error causes, and event histories.
[Diagnostics]
[CC IE
Field Diagnostics]
Page 118 Diagnosing
CC-Link IE Field Network
Reset operation
Reset the board.
[Online]
[Reset
Operation]
Summary of Contents for MELSEC Q80BD-J71GF11-T2
Page 2: ......
Page 6: ...4 Disposal Precautions CAUTION When disposing of this product treat it as industrial waste ...
Page 118: ...116 12 MONITORING MEMO ...
Page 140: ...138 14 MELSEC DATA LINK LIBRARY MEMO ...
Page 142: ...140 15 PROGRAMMING 15 1 Precautions on Programming MEMO ...
Page 243: ...241 I U Utility 83 ...
Page 247: ......