![Mitsubishi Electric MELSEC Q80BD-J71GF11-T2 User Manual Download Page 194](http://html.mh-extra.com/html/mitsubishi-electric/melsec-q80bd-j71gf11-t2/melsec-q80bd-j71gf11-t2_user-manual_238449194.webp)
192
APPX
Appendix 3 Link Special Relay (SB) List
SB0072
Scan mode setting
information
Stores the scan mode setting status.
• OFF: Asynchronous mode
• ON: Synchronous mode
SB0074
Reserved station
specification status
Stores the reserved station specification status due to parameters. The station
number set for a reserved station can be checked by Reserved station specification
(SW00C0 to SW00C7).
• OFF: Not specified
• ON: Specified
SB0075
Error invalid station
setting status
Stores the Error invalid station setting status due to parameters. The station number
set for the error invalid station can be checked by Error invalid station setting
(SW00D0 to SW00D7).
• OFF: Not specified
• ON: Specified
SB0077
Parameter reception
status
Stores the parameter reception status from the master station.
• OFF: Reception completed
• ON: Reception not completed
SB0078
Loopback function
setting status
Stores the setting status of the loopback function configured by the parameter
• OFF: Not used
• ON: Used
SB007A
Event history status
Stores the network event history occurrence.
• OFF: No event history
• ON: Event history found
If the event history is found, the cumulative number of network event history can be
checked by the Event count (SW007A).
Depending on the timing of the link refresh, the update of Event count (SW007A) may
be offset by one sequence scan.
This area is cleared when Event count clear (SB0009) is turned ON.
SB007B
Input data status of
data link faulty
station
Stores the own station's setting status for "Data Link Faulty Station Setting".
• OFF: OFF or cleared to 0
• ON: Hold
SB007D
Hold/clear status
setting for CPU
STOP
Stores the own station's setting status for "Output Setting during CPU STOP".
• OFF: Hold
• ON: Clear (ALL OFF)
SB008C
PORT1 error frame
reception status
(own station) (2)
Stores if a receive frame error line status warning level has occurred in the own
station's PORT1.
• OFF: A receive frame error line status warning level has not yet been occurred.
• ON: A receive frame error line status warning level has been occurred.
SB008D
PORT2 error frame
reception status
(own station) (2)
Stores if a receive frame error line status warning level has occurred in the own
station's PORT2.
• OFF: A receive frame error line status warning level has not yet been occurred.
• ON: A receive frame error line status warning level has been occurred.
SB008E
PORT1 error frame
reception detection
status (own station)
(latch) (2)
Stores if a receive frame error line status warning level has occurred in the own
station's PORT1 from power-on until the present.
• OFF: A receive frame error line status warning level has not yet been occurred.
• ON: A receive frame error line status warning level has been occurred.
SB008F
PORT2 error frame
reception detection
status (own station)
(latch) (2)
Stores if a receive frame error line status warning level has occurred in the own
station's PORT2 from power-on until the present.
• OFF: A receive frame error line status warning level has not yet been occurred.
• ON: A receive frame error line status warning level has been occurred.
SB0090
Hardware test
completion status
Stores the hardware test completion status.
• OFF: Not executed or execution in progress
• ON: Completed
If completed, the completion status can be checked by Hardware test normal/
abnormal end (SB0091).
SB0091
Hardware test
normal/abnormal
end
Stores the hardware test normal completion or abnormal completion status.
• OFF: Normal completion
• ON: Abnormal completion
(Conditions)
This is enabled when Hardware test completion status (SB0090) is ON.
SB0092
Self-loopback test
completion status
Stores the self-loopback test completion status.
• OFF: Not executed or execution in progress
• ON: Completed
If completed, the completion status can be checked by Self-loopback test normal/
abnormal end (SB0093).
Number
Name
Description
Availability
Master
station
Local
station
Summary of Contents for MELSEC Q80BD-J71GF11-T2
Page 2: ......
Page 6: ...4 Disposal Precautions CAUTION When disposing of this product treat it as industrial waste ...
Page 118: ...116 12 MONITORING MEMO ...
Page 140: ...138 14 MELSEC DATA LINK LIBRARY MEMO ...
Page 142: ...140 15 PROGRAMMING 15 1 Precautions on Programming MEMO ...
Page 243: ...241 I U Utility 83 ...
Page 247: ......