Appendix 1 Precautions for Accessing Redundant CPU System
181
A
■
Details of the special relay and special registers to be monitored when estimating the
occurrence of path switching
No.
Name
Description
Description details
SM1600
Other system error flag
OFF: No error
ON: Error
• Turns ON when an error occurs by redundant system error check. (Turns ON when
any of bits for SD1600 turns ON.)
• Remains OFF when no errors are present.
SD1590
No. of module for which
system switching request
is issued from the network
module in own system
No. of module for which
system switching request
is issued from the network
module in own system
• Any of the following bits turns ON corresponding to the No. of the module for which
system switching request is issued from the network module in own system.
• Turned OFF by the system after the error of the relevant module is resolved by the
user.
• For No. of module for which system switching request is issued from the network
module in another system, refer to SD1690.
SD1690
No. of module for which
system switching request
is issued from the network
module in another system
No. of module for which
system switching request
is issued from the network
module in another system
• Any of the following bits turns ON corresponding to the No. of the module for which
system switching request is issued from the network module in another system.
• Turned OFF by the system after the error of the relevant module is resolved by the
user.
• For No. of module for which system switching request is issued from the network
module in own system, refer to SD1590.
SD1590
0
0/1
0/1 0
b15
b11
b1 b0
0 : OFF
1 : ON
Each bit
Disabled since a CPU
module uses two slots.
Module No.0 :
Module No.1 :
Module No.11:
Module to the right of a
CPU module
Rightmost module on
12-slot base unit (Q312B)
to
to
SD1690
0
0/1
0/1 0
b15
b11
b1 b0
0 : OFF
1 : ON
Each bit
Disabled since a CPU
module uses two slots.
Module No.0 :
Module No.1 :
Module No.11:
Module to the right of a
CPU module
Rightmost module on
12-slot base unit (Q312B)
to
to
Summary of Contents for MELSEC Q80BD-J71GF11-T2
Page 2: ......
Page 6: ...4 Disposal Precautions CAUTION When disposing of this product treat it as industrial waste ...
Page 118: ...116 12 MONITORING MEMO ...
Page 140: ...138 14 MELSEC DATA LINK LIBRARY MEMO ...
Page 142: ...140 15 PROGRAMMING 15 1 Precautions on Programming MEMO ...
Page 243: ...241 I U Utility 83 ...
Page 247: ......