Appendix 4 Link Special Register (SW) List
201
A
SW0047
Baton pass status
(own station)
Stores the baton pass status for the own station (transient transmission possible).
• 0: Data link in progress
• 2: Baton pass in progress
• 3: Baton pass stopped
• 4: Test in progress
• 5: Offline
SW0048
Cause of baton pass
interruption
Stores the cause of interruption in the communication (baton pass) of own station.
• 00H: At normal communication or power-on
• 30H: Cable disconnection
• 33H: Disconnection or reconnection in progress
• 40H: Offline mode
• 41H: Hardware test
• 42H: Self-loopback test
SW0049
Cause of data link
stop
Stores the cause which stopped the data link of own station.
• 00H: At normal communication or power-on
• 01H: Stop command issued
• 02H: Monitoring timeout
• 05H: No slave stations (master station only)
• 10H: Parameter not received (local stations only)
• 11H: Own station number out of range
• 12H: Own station specified as reserved
• 13H: Station number duplication (own station)
• 14H: Master station duplication
• 16H: Station number not set
• 18H: Parameter error
• 19H: Parameter communication in progress
• 1AH: Station type mismatch
• 20H: CPU module stop error
• 60H: Incorrect ring topology configuration (master station only)
SW004A
Data link stop
request station
Stores the station number of the station that performed the cyclic transmission stop
request for the own station.
• Range: 125 (master station), 1 to 120 (local station)
The cyclic transmission stop request is performed by System link stop (SB0003).
(Conditions)
This is enabled when the Baton pass status (own station) (SB0047) is OFF.
SW004B
Own station's CPU
status
Stores the own station's status.
• 00H: No module mounted
• 01H: STOP (Normal)
• 02H: STOP (Stop error occurring)
• 03H: STOP (Continuation error occurring)
• 04H: RUN (Normal)
• 05H: RUN (Continuation error occurring)
• 06H: STEP-RUN
• 07H: PAUSE
• 0EH: Reset in progress
• 0FH: Initial processing
SW004C
Parameter setting
status
Stores the parameter status.
• 0: Normal
• 1 or higher: Abnormal (
(Conditions)
This is enabled when the Received parameter error (SB004D) is ON.
SW0050
Data link start status
(own station)
Stores the results when cyclic transmission is started by Link start (own station)
(SB0000).
• 0: Normal
• 1 or higher: Abnormal (
When Link start (own station) (SB0000) is turned OFF, the stored error definition is
cleared.
(Conditions)
This is enabled when the Baton pass status (own station) (SB0047) is OFF.
Number
Name
Description
Availability
Master
station
Local
station
Summary of Contents for MELSEC Q80BD-J71GF11-T2
Page 2: ......
Page 6: ...4 Disposal Precautions CAUTION When disposing of this product treat it as industrial waste ...
Page 118: ...116 12 MONITORING MEMO ...
Page 140: ...138 14 MELSEC DATA LINK LIBRARY MEMO ...
Page 142: ...140 15 PROGRAMMING 15 1 Precautions on Programming MEMO ...
Page 243: ...241 I U Utility 83 ...
Page 247: ......