Appendix 15 EMC and Low Voltage Directives
Cables
Use a shielded cable for the cable extended out of the control panel.
If a shielded cable is not used or not grounded correctly, the noise immunity will not meet the required value.
■
CC-Link IE Field Network cables
The precautions for using CC-Link IE Field Network cables are described below.
• Use CC-Link IE Field Network cables (SC-E5EW-S
M, manufactured by Mitsubishi Electric System & Service Co., Ltd.).
• A CC-Link IE Field Network cable is a shielded cable. Remove a part of the shield as shown below and ground the largest
possible exposed section to the ground.
■
Grounding cables with a cable clamp
Ground the shield of the external wiring cable to the control panel with the AD75CK cable clamp (Mitsubishi). (Ground the
shield within 20 to 30cm from the module.).
For details on the AD75CK, refer to the following manual.
AD75CK-type Cable Clamping Instruction Manual
Shield
CC-Link IE Field Network cable
AD75CK
CC-Link IE Field Network board
Inside the control panel
20 to 30cm