16 TROUBLESHOOTING
16.9 Error Code List
167
16
16.9
Error Code List
The list of error codes is shown.
For error codes which are not listed in this section, refer to the following manual.
MELSEC Data Link Library Reference Manual
MELSEC-Q CC-Link IE Field Network Master/Local Module User's Manual
If the error still occurs after the corrective action, please consult your local Mitsubishi representative.
For information required for inquiries, refer to the following section.
Page 166 Information Required for Inquiries
Error
code
Error code
Corrective action
D000H to
D00FH
Hardware error
Refer to corrective action for hardware error. (
D010H to
D013H
Parameter error
Correct the points assigned to the link devices.
D014H to
D016H
Hardware error
Refer to corrective action for hardware error. (
D018H
Parameter error
Correct the constant link scan time.
D019H to
D020H
Hardware error
Refer to corrective action for hardware error. (
D030H to
D035H
Connection failure
Correct the wiring condition.
D036H
Hardware error
Refer to corrective action for hardware error. (
D037H
Connection failure
Check the number of connected modules.
D040H
Hardware error
Refer to corrective action for hardware error. (
D041H
Connection failure
Check the number of connected modules.
D080H to
D084H
Hardware error
Refer to corrective action for hardware error. (
D0A0H
Transient data transmission
response wait timeout
If the own station or target station is disconnected from the network, identify the cause of the
disconnection and take action.
When the mode of the master station is "Online (High Speed Mode)", change it to "Online (Normal
Mode)" and retry the operation.
When the target station is overloaded and cannot receive transient data, reduce the frequency of
transient transmission and retry the operation.
D0A1H
Transient data transmission
completion wait timeout
Check if the cables and switching hub are connected properly.
Exchange the cables between PORT1 and PORT2 and retry the operation.
Reduce the frequency of transient transmission and then retry the operation.
Perform hardware and self-loopback tests. (
Page 48 Hardware test, Page 49 Self-loopback test)
D0A2H
Transient data transmission
processing wait timeout
Reduce the frequency of transient transmission and then retry the operation.
Check if the cables and switching hub of the request source are connected properly.
D0A3H
Transient data transmission error
If the own station or target station is disconnected from the network, identify the cause of the
disconnection and take action.
Correct the target station number of the transient data, and retry the operation.
If the target station of the transient data resides in another network, check if the routing parameters for
respective stations are correctly set, and take corrective action.
D0A4H to
D0A6H
Transient transmission failed
Check if the cables and switching hub are connected properly.
Exchange the cables between PORT1 and PORT2 and retry the operation.
Reduce the frequency of transient transmission and then retry the operation.
Perform hardware and self-loopback tests. (
Page 48 Hardware test, Page 49 Self-loopback test)
D0A7H
Transient reception failed
D0C0H to
D0D0H
Process error
The error has occurred in the following process. Wait for a while, and retry the operation.
• D0C0H: Reserved station specification
• D0C1H: Disabling the reserved station
• D0C2H: Data link stop instruction
• D0C3H: Data link start instruction
• D0C4H: Temporary error invalid station setting
• D0C5H: Cancellation of temporary error invalid station setting
• D0C6H: Change of other station number setting
• D0D0H: Other station number setting
D0E0H
Station type mismatch
In "Network Configuration Setting" of the master station, change the station type to that of the own
station.
Summary of Contents for MELSEC Q80BD-J71GF11-T2
Page 2: ......
Page 6: ...4 Disposal Precautions CAUTION When disposing of this product treat it as industrial waste ...
Page 118: ...116 12 MONITORING MEMO ...
Page 140: ...138 14 MELSEC DATA LINK LIBRARY MEMO ...
Page 142: ...140 15 PROGRAMMING 15 1 Precautions on Programming MEMO ...
Page 243: ...241 I U Utility 83 ...
Page 247: ......