Appendix 5 Processing Time
217
A
Link scan time
The following is a calculation formula for the link refresh time. (when the link scan mode is asynchronous)
Transmission delay time
The following are the calculation formulas for the transmission delay time.
Master station (RX)
←
Slave station (input)
The following table shows the time after a signal is input to the slave station until the board device of the master station turns
ON or OFF.
SM: Master station link refresh time
LS : Link scan time
Master station (RY)
→
Slave station (output)
The following table shows the time after the board device is turned ON or OFF until the output of the slave station is turned
ON or OFF.
SM: Master station link refresh time
LS : Link scan time
Item
Cyclic transmission mode
Normal mode
High speed mode
Ka
25.8
• When "Turn OFF or 0 Clear Input Data (RX/RY)" is set
in the network operation setting: 18.5
• When "Hold Input Data (RX/RY)" is set in the network
operation setting: 9.75
Kb
655
168
Kc
(Maximum transient processing time)
160 + 60
×
Total number of slave stations set in
the parameters
80
Kd
(Maximum data link processing time when
disconnecting from network or reconnecting to
network)
• When the serial number (first five digits) of the master station is '17022' or higher: Number of
disconnected stations
×
3500
• When the serial number (first five digits) of the master station is '17021' or lower: 9000 + Total number of
ports used in the switching hub
×
3000 (9000 when the switching hub is not used)
Calculation value
Calculation formula
Normal value
SM
×
0.5 + LS
×
1 + slave station response time [ms]
Maximum value
SM
×
1 + LS
×
2 + slave station response time [ms]
Calculation value
Calculation formula
Normal value
SM + LS
×
1 + slave station response time [ms]
Maximum value
SM + LS
×
2 + slave station response time [ms]
8
2
LS =
0.08
+
+
0.02 [ms]
RY points
RX points
(RWr RWw points)
(Number of connected slave stations
Ka)
Kb
Kc
Kd
(Number of event conditions in Event Setting)
1000
Ka)
Kb
Kc
Kd
Summary of Contents for MELSEC Q80BD-J71GF11-T2
Page 2: ......
Page 6: ...4 Disposal Precautions CAUTION When disposing of this product treat it as industrial waste ...
Page 118: ...116 12 MONITORING MEMO ...
Page 140: ...138 14 MELSEC DATA LINK LIBRARY MEMO ...
Page 142: ...140 15 PROGRAMMING 15 1 Precautions on Programming MEMO ...
Page 243: ...241 I U Utility 83 ...
Page 247: ......