6 WIRING
6.3 Wiring Product
47
6
6.3
Wiring Product
Applicable wires and cables
Use the following wires or cables connected to the transmission cable terminal block.
Wire ferrule
Bare cables can be connected to the transmission cable terminal block; however, for safety reasons, it is recommended to
connect wire ferrules.
Use UL-listed wire ferrules and, for processing, use a tool recommended by their manufacturer.
Classification
Name
Wire size
Temperature rating
Transmission cable (DP, DN)
UL-listed general-purpose 2-wire cable (VCTF, VCT)
1.25
70
or higher
0.75
UL-listed general-purpose wire
1.25
0.75
Dedicated flat cable
1.25
90
0.75
Power supply cable (24V, 0V)
UL-listed general-purpose 2-wire cable (VCTF, VCT)
0.75
to 2.0
70
or higher
UL-listed general-purpose wire
0.75
to 2.0
Dedicated flat cable
1.25
90
0.75
Type
Model
Application
Contact
Wire ferrule
AI 0,75-10 GY
Processing of a 0.75
wire
PHOENIX CONTACT GmbH & Co. KG
AI 1,5-10
Processing of a 1.25
wire