4 FUNCTION
4.5 Same ID Used Detection Function
27
4
How to recover from same ID used status
Check 'Number of the alarm IDs' (Un\G9984) and 'Alarm ID information storage area' (Un\G9985 to Un\G10112). Then set a
unique ID (address) in all the slave modules. (
Page 78 Number of the alarm IDs, Page 78 Alarm ID information storage
area)
Set IDs (addresses) of slave modules and execute automatic address detection of the FX5-ASL-M. Then, the IDs of the slave
modules are stored in the FX5-ASL-M and the error is cleared. (
Page 55 Automatic Address Detection Function)
Precautions
While an ID (address) is used for multiple slave modules, executing either of the following can eliminate the same ID used
error. However, the address is still used for the multiple slave modules.
• Powering off and on the AnyWireASLINK system
• Turning off and on 'Error flag clear command' (Un\G27 b0)