C-86
12.8 Function Selection
When the functions of the Lossnay unit were changed by function selection after installation, always indicate the set contents by entering or
other mark in the appropriate check field of the tables shown in page 7 and 8. (Settings may be lost if the remote controller malfunctions.)
When replacing a remote controller, specify the same settings as before the replacement.
NOTE
Function selection of remote controller
The setting of the following remote controller functions can be changed using the remote controller function selection mode. Change the setting
when needed.
Item 1
Item 2
Item 3 (Setting content)
[1] Change Language
(“CHANGE LANGUAGE”)
Language setting to display
Display in multiple languages is possible.
[2] Function limit
(“FUNCTION
SELECTION”)
(1) Operation function limit setting (operation lock)
(“LOCKING FUNCTION”)
Setting the range of operation limit (operation
lock)
(2) 24-hour ventilation setting*
2
*
6
(“24HR VENTILATION”)
Sets whether the [
ON/OFF] button stops
operation completely or initiates Extra low operation.
[3] Mode selection
(“MODE SELECTION”)
(1) Use of clock setting*
3
(“CLOCK”)
Setting the use or non-use of clock function
(2) Timer function setting
(“WEEKLY TIMER”)
Setting the timer type
(3) Contact number setting for error situation
(“CALL.”)
Contact number display in case of error
Setting the telephone number
[4] Display change
(“DISP MODE SETTING”)
(1) Filter cleaning setting
(“MAINTENANCE SIGN”)
(SW5-5)*
5
Set the schedule for “FILTER” indicator to appear
after 3000-hour use, or no indication
(2) Lossnay cores cleaning setting
(“MAINTENANCE SIGN”)
Set the schedule for “CORE” indicator to appear
after 6000-hour use, or no indication
(3) SA (Supply Air) Temperature display setting
(“TEMPERATURE DISP”)
Sets whether the SA (Supply Air) Temperature
(Calculated value) display or not.
(4) OA (Outdoor Air) Temperature display setting
(“TEMPERATURE DISP”)
Sets whether the OA (Outdoor Air) Temperature (measured
at the sensor in the LOSSNAY unit) display or not.
(5) RA (Room Air) Temperature display setting
(“TEMPERATURE DISP”)
Sets whether the RA (Room Air) Temperature (measured
at the sensor in the LOSSNAY unit) display or not.
(6) Temperature cxchange efficiency setting
(“EXCHANGE EFFICIENCY”)
Sets whether the temperature exchange
efficiency.
[5] Installation settings*
1
*
2
(“LOSSNAY FUNCTION”)
(1) Supply fan speed setting
(“SA SETTING”)
(SW2-4,9)*
5
Sets Extra High/High fan speed selection , and
Multi Ventilation modes
(2) Exhaust fan speed setting
(“EA SETTING”
)
(SW2-5,10)*
5
Sets Extra High/High fan speed selection , and
Multi Ventilation modes
(3) Power supply/exhaust when operation starts
(“POWER VENT START”)
(SW2-3)*
5
Switching to power supply/exhaust when
operation starts
(4) Subordinate Lossnay settings*
4
(“
SUB
SET”)
Enable/disable subordinate Lossnay unit supply
and exhaust fan speed settings.
(5) Power supply ON/OFF/AUTO
(“RECOVERY SETTING”)
(SW2-6)*
5
(SW5-4)*
5
Controls stop and start operation by turning the
power supply (220-240 V) for the Lossnay on and off.
(6) Operation monitor output selection
(“OPERATION MONITOR”)
(SW5-2)*
5
Sets whether the operation monitor will apply to
the exhaust fan or the supply fan.
(7) Exhaust fan speed selection for cold region
intermittent operation (“EA SETTING INTERMIT”)
(SW5-9)*
5
Sets exhaust fan speed for cold region
intermittent operation.
(8) Night purge setting*
3
(“NIGHT PURGE”)
Enables/disables Night purge.
(9) Bypass automatic ventilation priority setting
(“BYPASS SETTING”)
(SW2-7)*
5
Selects the auto ventilation adjustment (AUTO)
pattern.
[6] Interlocking settings*
1
*
2
(“INTERLOCK SETTING”)
(1) Interlock mode setting
(“INTERLOCK MODE”)
(SW5-7,8)*
5
These settings indicate how Lossnay should operate
when external devices are started or stopped.
(2) Pulse input setting
(“INPUT SIGNAL”)
(SW2-2)*
5
Set when pulse signal equipment is connected to
an external input.
(3) Delayed operation settings
(“DELAY OPERATION”)
(SW5-1)*
5
Setting for delay (of operation at startup of
heating or cooling)
(4) Exhaust operation settings for air conditioner
defrosting (“EA SETTING DEFROST”)
(SW5-3)*
5
Stopping exhaust fan when defrosting air
conditioner
[5] Installation settings and [6] Interlocking settings are selection modes that allow overriding of Lossnay unit Dip switches settings via remote
controllers.
*
1
When a remote controller is set to factory setting, the system operates according to the main unit Dip switch settings. When the remote controller settings are changed
from the defaults, the system operates according to those settings. (The main unit switch settings are overridden.)
*
2
If two remote controllers are used, these settings can be performed only for the “main” remote controller. These settings will be skipped for the “sub” remote controller
and may not be modified. The designation of main and sub remote controller and are determined automatically upon main unit power-up. The remote controller for
which [5] and [6] are displayed in the Function Selection mode is the main remote controller.
*
3
Clock use must be set for Weekly timer and Night purge operation.
*
4
Applies only to the following functions:
[Supply fan], [Exhaust fan], [Start up power supply and exhaust]
*
5
Indicates Dip switches in the Lossnay control box.
*
6
For the Lossnay models without those functions, those setting items will be nondisplay.