C-30
M-NET transmission
cable
Lossnay
MA remote
controller
Indoor unit
of air conditioner
Indoor unit
of air conditioner
PZ-60DR-E
5.12 When connecting to the City Multi, Lossnay
remote controller (PZ-52SF-E) or Mitsubishi
Electric Air-Conditioner Network System
(MELANS)
If centralized control is performed according the wire connection shown in this section, the remote controller (PZ-41SLB-E) can-
not be used.
When interlocking with Mitsubishi Free Plan air conditioner
S
B
A
TB5
M-NET transmission cable
Shielded wire
M-NET transmission cable input terminal block
●
Incase of PZ-60DR-E
M-NET transmission
cable
Lossnay
MA remote
controller
Indoor unit
of air conditioner
Indoor unit
of air conditioner
PZ-52SF-E
●
Incase of PZ-52SF-E
Power
supply unit
Lossnay
MELANS
M-NET transmission cable
(Optional)
PZ-60DR-E
When connecting to PZ-60DR-E and MELANS
●
Connect the power feeding unit.
* Limit the total length of transmission wires no longer than 500 m.
Limit the wiring length between Lossnay and the power supply
unit (Optional) or the outdoor unit no longer than 200 m.
●
One shielded wire is connected to TB5
S
on the PCB on terminal.Address setting is required. (Refer to function setting section.)
M-NET transmission cable: Connect any of the City Multi indoor unit, or Mitsubishi Electric Air-Conditioner Network System
(MELANS) - to the Lossnay.
●
Connecting positions are different for the Remote Controller PZ-60DR-E and PZ-52SF-E.
PZ-60DR-E
:
Connect to TM4
1
,
2
on the PCB. (Refer to page C-71 “When connecting with Remote Controller (PZ-60DR-E)”.)
PZ-52SF-E
:
Connect to TB5
A
,
B
on the same terminal block as for theM-NET transmission wires.
●
Securely connect the M-NET transmission wires to TB5
A B
.(No-Polar)
Type: (Shielded wire, CVVS/CPEVS)
Wire diameter: 1.25 mm
2
to 2.0 mm
2
CAUTION:
●
Don’t tighten screws on the terminal block with a torque larger than 0.5 Nm. It may damage the PCB.
●
Always use shielded wires only for the M-NET transmission wires, and finish the shield properly.
Summary of Contents for LGH-100RX5 -E
Page 1: ...Lossnay Remote Controller ...
Page 2: ......
Page 94: ...C 94 ...
Page 95: ...C 95 5 ...
Page 96: ...C 96 ...
Page 97: ...C 97 ...
Page 98: ...C 98 5 3 ...
Page 99: ...C 99 ...
Page 106: ...Y08 004 Jan 2009 MEE ...