C-12
4.4.3 Operation with two Remote controllers
System Example
Operation Method
The operation is the same with each remote controller. In this case, the Lossnay gives operating priority to the last button push.
Characteristics
Remote controller
Note
• Lossnay can be operated from two remote locations.
• Use only up to two remote controllers
• Lossnay conditions can be checked from two remote Lossnay remote controller
(Operation will not go normally if three
locations.
PZ-60DR-E, PZ-41SLB-E
remote controller switches are con-
• The remote controller gives priority to the last touch.
nected.)
Lossnay
Power supply
Lossnay
Power supply
Transmission
cable extension
is 500 m or less
0.65 to 1.2
PVC cable or
0.3 mm
2
to 1.25 mm
2
strand wire.
MAX 15 units.
Remote controller
PZ-60DR-E or PZ-41SLB-E
Transmission
cable extension
is 500 m or less
0.65 to 1.2
PVC cable or
0.3 mm
2
to 1.25 mm
2
strand wire.
Lossnay
Power supply
Lossnay
Power supply
Lossnay
Power supply
Lossnay
Power supply
MAX 15 units.
Remote controller
PZ-60DR-E or PZ-41SLB-E
Remote controller
PZ-60DR-E or
PZ-41SLB-E
Remote controller
PZ-60DR-E or
PZ-41SLB-E