C-103
15.3.1 Operating Lossnay with ME remote Controller
(When Interlocked with City Multi Indoor Unit)
Operation method is same as A-control remote controller. Refer to page C-100.
15.3.2 Initial registration mode
Register the address of the indoor unit with the remote controller.
1
Stop the remote controller by pressing the [ON/OFF] button.
•
If the indoor unit is not registered, “HO” appears in the room temperature display. Follow step 2.
2
Display “INDOOR UNIT ADDRESS NO.”
•
Press and hold down the [FILTER] button (shown as
A
) and the “Louver” button (shown as
B
) simultaneously for two
seconds.
15.3 ME Remote Controller (PAR-F27MEA)
INDOOR UNIT
ADDRESS NO.
INDOOR UNIT
ADDRESS NO.
OA UNIT ADDRESS NO.
INDOOR UNIT
ADDRESS NO.
OA UNIT ADDRESS NO.
Both “INDOOR UNIT ADDRESS NO.” and “OA
UNIT ADDRESS NO.” will appear simultaneously.
E
A
B
D
H
G
C
F
PAR-F27MEA
ON/OFF
CENTRALLY CONTROLLED
DAILY
AUTO OFF
REMAINDER
ERROR CODE
CLOCK
ON
OFF
CHECK MODE
FILTER
TEST RUN
1Hr.
NOT AVAILABLE
STAND BY
DEFROST
FILTER
CHECK TEST
TEMP.
TIMER SET
CLOCK
→
ON
→
OFF
LIMIT TEMP.
•
Use the
and
[TEMP] buttons (shown as
C
) to select the address of the indoor unit to be interlocked.
•
Use the
and
[TIMER SET] buttons (shown as
H
) to select the address of the Lossnay unit to be regis-
tered.
15.3.3 Interlocked registration
3
Display the “OA UNIT ADDRESS NO.”
•
Press the “Operation mode” button (shown as
G
).
Press once again to return to “INDOOR UNIT ADDRESS NO.” shown in Step
2
.
Summary of Contents for LGH-100RX5 -E
Page 1: ...Lossnay Remote Controller ...
Page 2: ......
Page 94: ...C 94 ...
Page 95: ...C 95 5 ...
Page 96: ...C 96 ...
Page 97: ...C 97 ...
Page 98: ...C 98 5 3 ...
Page 99: ...C 99 ...
Page 106: ...Y08 004 Jan 2009 MEE ...