C-19
4.6.3 MA Remote Controller/ME Remote Controller in Combination
with Lossnay Non-M-NET Remote Controller (PZ-60DR-E)
System
Combining MA, ME and Lossnay Non M-NET remote controllers is permitted.
●
In case of combination with Lossnay M-NET remote controller (PZ-52SF-E) please refer LGH-RX
4
Technical Manual.
Combining Indoor Unit of Air Conditioner Remote Control and Lossnay Remote Control
Indoor unit of
air conditioner
(001)
Lossnay
(002)
MA remote
controller
(101)
Outdoor unit
(051)
Power
supply
unit
G
G
Interlocked operation setting
( ) address
Centralized controller (000)
Lossnay remote
controller
PZ-60DR-E
Indoor Unit
Lossnay LGH-RX
5
type
Model for MA remote control (Type C or later)
«
Model for other than MA remote control (Type B or earlier)
×
«
:
Compatible
×
:
Incompatible
System Examples: 1
Setting Method
(1) Make the Group setting for the indoor unit.
(2) Make the Group setting for the Lossnay unit.
(3) Set the indoor unit and Lossnay unit for interlocked operation.
When using the centralized controller, make both the Group setting and operation setting with centralized controller.
Characteristics
(1) When the indoor unit is set for interlocked operation in one group:
Interlocked Lossnay operation is possible with indoor unit remote controller. In this case, operation can switch between
High/Low/Off. It is possible to switch Lossnay operation only between High/Low/Off with the indoor unit remote controller.
It is possible to controll the Lossnay unit from Lossnay remote controller PZ-60DR-E. More additional function such as Extra
Low fan speed is available.
(2) When two or more indoor units in different groups are set for interlocked operation, the Lossnay will operate if at least one
group operates. The Lossnay will stop operation if all groups stop operation.
It is possible to switch the Lossnay only between High/Low when other groups are operating with indoor unit remote con-
troller.
It is possible to controll the Lossnay unit from Lossnay remote controller PZ-60DR-E. More additional function such as Extra
Low fan speed is available.
Note:
●
If the display on the MA, ME or other indoor unit remote controllers is cancelled, the indoor unit remote controller will not
show the ventilation display even if Lossnay is operating via the Lossnay remote controller PZ-60DR-E.
Note:
Power supply limitation of transmission cable for indoor unit.
●
Indoor units + ME remote controllers (compact remote controllers) is less than or equal to 40 units.
●
Indoor units are less than or equal to 20 units.
(MA remote controllers and Lossnay units are not included in the 20 units, listed above.)