C-21
Operation
Monitoring
Contents
ON/OFF
Switch fan to High/Low
Switch ventilation mode
Prohibit local ON/OFF operation
Operation condition
Fan speed
Ventilation mode (conditions)
Errors
Filter maintenance indicator
Prohibit local ON/OFF operation
Individual Lossnay
(Lossnay not set
for interlocked
operation)
«
«
«
«
«
«
«
«
«
«
Interlocked Lossnay
(Lossnay set for
interlocked opera-
tion with City Multi)
×
×
×
×
×
×
×
«
×
×
4.6.4 When Using the LONWORKS
®
Compatible Adaptor (LMAP02-E)
to Connect to LONWORKS
®
By using the LON
®
adaptor (model name: LMAP02-E) to connect to LONWORKS
®
, it is possible to control and observe Lossnay
operation on a building management system.
* For specifications and functions of the LON
®
adaptor, refer to the materials regarding the LONWORKS
®
compatible adaptor.
Table of Functions
System Example
(Using M-NET)
Lossnay
Lossnay
Building
management
system
LMAP02-E
Lossnay
remote controller
PZ-60DR-E
Lossnay
remote controller
PZ-60DR-E
M-NET
LONWORKS
M-NET
Lossnay
Lossnay
LMAP02-E
Lossnay
remote controller
PZ-60DR-E
Lossnay
remote controller
PZ-60DR-E
Connect the M-NET transmission cable to TB5 A,B of the Lossnay terminal block. (Refer to page C-71).
The Lossnay remote controller (PZ-41SLB-E) cannot be used with this system.
Up to 50 units can be connected with one LMAP02-E.
For details about the system or connection cables of the LMAP02-E, refer to its technical materials.
* LONWORKS
®
is a registered international trademark, registered in the U.S.A. to the Echelon Corporation.
«
: Available
×
: Not Available