C-48
«
Check the power supply to the
Lossnay. (Refer to Table 1-1-1)
«
Set the Main/Sub (SW1) switch
to “Main”.
«
Check the length of the trans-
mission cable wiring.
«
Check the number of units con-
nected.
«
Connect the transmission cable
to TM4
1
,
2
.
«
Change to the PZ-60DR-E or
PZ-41SLB-E remote controller.
1
No.
• Remote controller
display does not
appear.
• The power display
“
” does not
appear on the
remote controller.
• The remote con-
troller continues to
display “H0”.
«
Power is not supplied to the Lossnay, or power
that does not follow specifications is used.
«
When using only one Lossnay, the Main/Sub switch
(SW1) on the Lossnay circuit board is set to “Sub”.
«
The overall wiring length of the transmission cable
is longer than specified (longer than 500 m).
«
Is there a connection of 3 or more remote con-
trollers, or 16 or more Lossnay units?
«
The remote controller is connected to TB5 (termi-
nal block for M-NET transmission cable).
«
PZ-52SF-E (Lossnay remote controller for M-NET)
is connected to the Lossnay remote controller.
2
Remote controller
does not operate.
(Communication error
display)
«
When using multiple Lossnay units, the Main/Sub
switch (SW1) on the Lossnay circuit board of the
second or following unit is set to “Main.”
«
The overall wiring length of the transmission cable
is longer than specified (longer than 500 m).
«
Multiple transmission cables are wired with multi
core cables.
«
When two remote controllers are used, are PZ-
60DR-E and PZ-41SLB-E being used together?
«
Set the Main/Sub switch (SW1)
of the second and following
Lossnay units to “Sub”.
«
Check the length of the trans-
mission cable wiring.
«
Using suitable cables, wire the
transmission cables so that they
are separated from one another.
«
Use the same type of remote
controller.
3
Interlock operation
with external device
does not occur.
«
Is the specified power being supplied to the
Lossnay unit?
«
Are the signal cables from the external devices
wired according to regulations?
«
The type of external signal does not match the
connected terminal unit (charged, uncharged, seri-
al signal).
«
The type of external signal does not match the
pulse input setting (level signal, pulse signal).
«
The external device signal is not being input.
«
The external device and signal cable wiring is
longer than specified.
12 V DC, 24 V DC:
Longer than limitations of
external device
Uncharged a-contact:
Longer than 500 m
Mr. Slim signal:
Longer than 500 m
«
“DELAY OPERATION ‘ON’” (PZ-60DR-E) or
“Delay time” (PZ-41SLB-E) is set. (When using
PZ-60DR-E, during the delay operation, LED1
(green) on the Lossnay circuit board will be lit.)
«
Refer to Table 1-1-1.
«
Refer to Table 1-1-3.
«
Check the type of external signal
and the connections between the
external signal and external con-
trol input terminal (TM2).
«
<When using PZ-60DR-E>
Check the type of external signal
and verify the pulse input setting
from the function selection.
(Refer to page C-66)
<When not using PZ-60DR-E>
Check the type of external signal
and the setting of the pulse input
switch (SW2-2) on the Lossnay
circuit board. (Refer to page C-73).
«
Check the external device.
«
Check the length of the signal
cable wiring.
«
Check the Delay operation set-
ting with the remote controller
(PZ-60DR-E or PZ-41SLB-E).
Error
Cause
Action
System checklist (Table 1-2)
When using PZ-60DR-E, PZ-41SLB-E, or interlocking with external devices (Table 1-2-1)