C-6
M-NET System
4.2
System Examples
Operating with an external device
●
Lossnay operation will be performed via the external device.
●
Level signal or pulse signal input (12V DC, 24V DC, uncharged a-con-
tact) is possible.
One Lossnay with one remote controller
●
A simple system in which Lossnay is operated
independently with one remote controller.
Multiple Lossnay units with one remote controller
●
Up to 15 Lossnay units can be controlled at
one time with one remote controller.
Two remote controller system with one Lossnay
●
Lossnay can be controlled from two remote
locations.
●
The remote controller gives priority to the last
operation function request.
Operating with Mr. Slim
●
The Lossnay remote controller (PZ-60DR-E, PZ-41SLB-E) cannot be
used with this system.
●
Use MA remote controller of Mr.Slim for switching Lossnay ON/OFF or
the fan speed.
●
The ventilation mode is “automatic ventilation”.
Basic System (Refer to page C-1
1)
Operation with an Air Conditioning Unit
(Refer to page C-13)
Operating with an External Device
(Refer to page C-22)
Lossnay
Remote controller
PZ-60DR-E or PZ-41SLB-E
Power supply
Non-polar
Two wires
Lossnay
Power supply
(Sub)
(Main)
Lossnay
Power supply
Non-polar
Two wires
Remote
controller
PZ-60DR-E or
PZ-41SLB-E
Lossnay
Power supply
Non-polar
Two wires
Remote controller
PZ-60DR-E or PZ-41SLB-E
Air conditioning device and system control
●
One Lossnay can be interlocked with 16 indoor units. In addition, PZ-60DR-E (non M-NET) can be connected for each Lossnay units.
Indoor
unit
MA remote controller
Outdoor unit
Indoor
unit
MA remote controller
Lossnay
Indoor
unit
MA remote controller
Lossnay
Indoor
unit
Indoor
unit
MA remote controller
Indoor
unit
MA remotecontroller
Lossnay
Indoor
unit
MA remote controller
Indoor
unit
MA remote controller
Lossnay
Indoor unit
Indoor
unit
Interlock-Group 1
Interlock-Group 5
Interlock-Group 3
Interlock-Group 4
Interlock-Group 2
Outdoor unit
Outdoor unit
Indoor
unit
MA remote
controller
Lossnay
Lossnay
Interlock-Group 1
Lossnay
Interlock-Group 2
Interlock-Group 3
Refrigerant 1
Refrigerant 2
・・・
Group setting
・・・
Interlocked
operation setting
●
Detailed control such as start/stop, fan speed Extra-Low and ventilation mode control is possible from the Lossnay remote controller PZ-60DR-E.
●
PZ-52SF-E (M-NET remote controller) can be used instead of PZ-60DR-E. However, function is limited and connecting position is different.
●
Start/stop, fan speed and ventilation mode control is possible from the centralized controller.
●
Controller can set up the group including maximum of 16 indoor or Lossnay units.
Lossnay
remote controller
PZ-60DR-E
Lossnay
Lossnay
Group 1
Lossnay
remote controller
PZ-60DR-E
Lossnay Lossnay
Lossnay
Lossnay
Group 3
Lossnay
remote controller
PZ-60DR-E
Lossnay
Group 4
Group 2
Centralized controller
Power
supply
unit
Lossnay
remote controller
PZ-60DR-E
Lossnay
Group 5
Lossnay
Power supply
Power supply
Remote
controller
Mr. Slim
(indoor unit)
Lossnay
Power supply
Power supply
Remote controller
Indoor unit
Non-polar
Two wires
Remote controller
PZ-60DR-E or
PZ-41SLB-E
City Multi and Lossnay Interlocked System
Centralized Management System
●
Selection of inter-
locked operation
mode is possible.
●
Delayed start inter-
locked operation is
possible.