C-70
Connect the power supply cable from the Electrically operated
damper to
9
and
0
of the monitor output terminal block (TM4)
with reference to the wire connection diagram.
Operation monitor output with delay function 1 can be possible.
(Refer to function settings 6 (Refer to C-74) “Setting for TM4
90
”)
Note:
•
Don’t tighten screws of
terminal block with a
torque larger than
0.5Nm. It could damage
the PCB.
•
Response times to external input signals are as shown in
the following table.
■
To force High fan speed externally
When SW1 is "ON", fan speed of the Lossnay will be set to
"High"(Extra-High) regardless of the remote control setting.
Use this in such a way that it ventilates at Low or Extra-Low
fan speed normally, and when the external sensor detects
contamination of indoor air, it changes to High (Extra High)
fan speed operation.
■
To force Low fan speed externally
When SW1 is "ON", fan speed of the Lossnay will be set to
"Low" regardless of the remote control setting.
Use this in such a way that it ventilates at High fan speed
normally, and when the external sensor detect that the indoor
air contamination is low, it changes to Low fan speed opera-
tion.
■
To force Extra-Low fan speed externally
When SW1 is "ON", fan speed of the Lossnay will be set to
"Extra-Low" regardless of the remote control setting.
Use this in such a way that it ventilates at High fan speed
normally, and when the external sensor detects that the
indoor air contamination is low, it changes to Extra-Low fan
speed operation.
* For the LGH-150RX
5
and LGH-200RX
5
types, fan speed of
the Lossnay will be “Low”.
External Signal Response Time
Level Signal
Max. 7 sec.
Pulse Signal
Max. 200 msec
0
9
Electrically
operated
damper
Power Supply
Lamp
Contactor rating
Max 240 VAC, 2 A
24 VDC,
2 A
Min
220 VAC, 100 mA
5 VDC,
100 mA
Monitor output
terminal (TM4)
SW1
CN16
CO
2
sensor, etc.
(When CO
2
increases: Closed)
SW1: High fan speed operation switch
(When closed: For High fan speed operation)
Remote display
adaptor (Optional)
PAC-SA88HA-E
Brown 1
Red 2
Orange 3
Yellow 4
Green 5
Not used. Insulate completely.
Max wiring length 10 m
Lossnay
control board
Fan speed/
Ventilation
mode selection
CO
2
sensor, etc.
(When CO dec
2
increases: Closed)
Remote display
adaptor (Optional)
PAC-SA88HA-E
Lossnay
control board
SW1
CN16
SW1: Low fan speed operation switch
(When closed: For Low fan speed operation)
Brown 1
Red 2
Orange 3
Yellow 4
Green 5
Not used. Insulate completely.
Max wiring length 10 m
Fan speed/
Ventilation
mode selection
Remote display
adaptor (Optional)
PAC-SA88HA-E
Lossnay
control board
SW1: Low fan speed operation switch
(When closed: For Low fan speed operation)
SW1
CN16
Brown 1
Red 2
Orange 3
Y
ellow 4
Green 5
Not used. Insulate completely.
Fan speed/
Ventilation
mode selection
Max wiring length 10 m
6. When connect to an Electrically operated damper, or take Operation monitor output
7.When switching High/Low/Extra-Low fan speed externally (when CO
2
sensor or other
equipment is connected)
Using marketed CO
2
sensor, etc., make connection by inserting the optional remote display adaptor (PAC-SA88HA-E) in the
connector CN16 (High/Low selector) as shown by the figure.
With SW1 is “ON”, the ventilation mode of Lossnay is changed
to the By-pass ventilation regardless of the setting on the
remote controller.
* When the outdoor air temperature drops lower than 8°C, it
changes to the heat exchanger ventilation. (Display of the
remote controller does not change.)
SW1
CN16
SW1: Bypass ventilation operation switch
(When closed: For Bypass ventilation operation)
Remote display adaptor
(Optional) PAC-SA88HA-E
Brown 1
Red 2
Orange 3
Yellow 4
Green 5
Not used. Insulate completely.
Lossnay
control board
Fan speed/
Ventilation
mode selection
Max wiring length 10 m
8.When switching By-pass externally
Establish the wire connection by inserting the optional remote display adaptor (PAC-SA88HA-E) in the connector CN16
(Ventilation mode selector).
Summary of Contents for LGH-100RX5 -E
Page 1: ...Lossnay Remote Controller ...
Page 2: ......
Page 94: ...C 94 ...
Page 95: ...C 95 5 ...
Page 96: ...C 96 ...
Page 97: ...C 97 ...
Page 98: ...C 98 5 3 ...
Page 99: ...C 99 ...
Page 106: ...Y08 004 Jan 2009 MEE ...