(1) Move the pulse input switch [SW2-2] to the ON
position.(Refer to function settings 1 (Refer to C-73)
“Settings for pulse input”.)
(2) Connect the pulse output device (i.e., building management
system) to the external control input terminal block [TM2].
• A pulse width of at least 200 msec will be needed.
• When using PZ-60DR-E, it can be set also from the remote controller.
Connecting methods vary depending on the types of pulse signal
Refer to Section 2 (Refer to C-67) “When the external device
has a charged operation signal of 12 VDC or 24 VDC” or “When
the external device has an uncharged a-contact signal”.
(1) Connect from Lossnay Unit 1 to Lossnay Unit 2, and from
Unit 2 to Unit 3 and so on up to a maximum of 15 units
using a transmission cable (PVC insulated PVC jacketed
and either between ø 0.65 and ø 1.2, or between 0.3 mm
2
and 1.25 mm
2
in cross section).
(2) Change the setting on the main/sub switch (SW1) on the
second and subsequent Lossnay units to “Sub”
.
CAUTION:
• Don’t tighten screws of terminal block with a torque larger
than 0.5 Nm. It could damage the PCB.
Note:
• Up to four 0.3 mm
2
stranded wires or ø 0.65 PVC wires can
be connected to one input terminal.
• For other types of wire, up to two can be connected.
• The operation signal and pulse signal can be connected to
the external device of the main Lossnay only.
• Connect the power to each respective Lossnay unit.
• When the LGH-150RX
5
and LGH-200RX
5
types are connected, they
operate at low fan speed even if extra low fan speed is selected.
1
2
SW2
3
4
5
6
7
8
9 10
ON
ON
OFF
Lossnay
(Main)
Power
supply
Exter nal
device
Operating switch for
external device
Remote controller
(PZ-60DR-E or PZ-41SLB-E)
Connect to remote
controller
(PZ-60DR-E or
PZ-41SLB-E)
Lossnay (Sub)
MAX 15 units
Power
supply
Lossnay (Sub)
Power
supply
Power
supply
Connect
to third
Lossnay
Main Sub
2
1
2
1
Transmission cable
First Lossnay
Second
Lossnay
TM4
(Factory setting: main)
TM4
3.When interlocking with a pulse output device
4.When operating multiple Lossnay units
Connect to
6
and
7
, or
7
and
8
of the monitor output termi-
nal block (TM3) with reference to the wire connection diagram.
Note:
•
Don’t tighten screws of terminal block with a torque larger
than 0.5Nm. It could damage the PCB.
By-pass or Delay 2 monitor output with delay function 2 can be
possible.
(Refer to function settings 13 (Refer to C-75) “Setting for TM3
67
”)
6
7
8
Lamp or
monitoring unit
Power
Supply
Monitor output terminal
TM3
Bypass operation signal
contactor rating
Max 240 VAC, 1 A
24 VDC,
1 A
Min
220 VAC, 100 mA
5 VDC,
100 mA
Malfunction signal
Malfunction indicator
Bypass operation indicator
5.When take Malfunction monitor output, or take By-pass operation monitor output