![Mitsubishi Electric Got 1000 User Manual Download Page 276](http://html.mh-extra.com/html/mitsubishi-electric/got-1000/got-1000_user-manual_240964276.webp)
18 - 4
18. TROUBLESHOOTING
18.1 GOT Restoration Sheet
(4) GOT restoration procedure
Follow the procedures below starting from (a) and in order to check if the GOT is restored.
If the GOT is not restored, proceed to the next item.
*1
When powering the GOT ON again (OFF
ON), power OFF the PLC before that.
(5) Troubled product investigation
When malfunction of the GOT is not improved, please contact your local Mitsubishi (Electric System) Service.
Depending on the problem details, we may ask you to return the troubled product to us.
In that case, please attach the GOT status check sheet, GOT installation status check sheet, and the system
configuration check sheet filled out with details of your system.
Check item
Cause
Action
(a) Press the GOT reset switch.
Restored
Not restored (Proceed to (b).)
The GOT may have malfunctioned
temporarily due to noise.
Take the action of (4)-(h).
(b) Power the GOT ON/OFF.
*1
Restored
Not restored (Proceed to (c).)
(c) Reset or power ON/OFF the PLC
CPU.
Restored
Not restored (Proceed to (d).)
(d) Power the GOT and PLC CPU ON/
OFF simultaneously.
Restored
Not restored (Proceed to (e).)
(e) Connect the cable again.
Restored
Not restored (Proceed to (f).)
The cable connection may be faulty.
Securely connect the cable.
If an error occurs again, proceed to (5)
Troubled product investigation.
(f) Reinstall the project data.
Restored
Not restored (Proceed to (g).)
Data may have been destroyed by an
action such as powering the GOT OFF
during the installation of project data or
OS.
Do not power the GOT OFF while
transferring data.
If an error occurs again, proceed to (5)
Troubled product investigation.
(g) Reinstall the OS.
Restored
Not restored (Proceed to (h).)
(h) Take the action described in the
"Action" column.
Restored
Not restored (Proceed to (i).)
The GOT may have malfunctioned
temporarily due to noise.
Take the action with referring to GOT
installation status check sheet.
(i) The GOT is not restored even by
performing (a) to (h).
-
Proceed to (5) Troubled product
investigation.
Summary of Contents for Got 1000
Page 1: ......
Page 2: ......
Page 14: ...A 12 ...
Page 26: ...1 4 1 OVERVIEW 1 1 Features ...
Page 34: ...2 8 2 SYSTEM CONFIGURATION 2 2 System Equipment ...
Page 38: ...3 4 3 SPECIFICATIONS 3 3 Power Supply Specifications ...
Page 42: ...4 4 4 PARTS NAME 4 3 Rear Face ...
Page 54: ...6 6 6 INSTALLATION 6 5 Installation Procedure ...
Page 104: ...10 18 10 COMMUNICATION INTERFACE SETTING COMMUNICATION SETTING 10 3 Ethernet Setting ...
Page 226: ...13 92 13 FILE DISPLAY AND COPY PROGRAM DATA CONTROL 13 2 Various Data Control ...
Page 250: ...15 2 15 CLEANING DISPLAY SECTION CLEAN ...
Page 264: ...16 14 16 INSTALLATION OF COREOS BOOTOS AND STANDARD MONITOR OS 16 5 CoreOS ...
Page 272: ...17 8 17 MAINTENANCE AND INSPECTION 17 5 Backlight Shutoff Detection ...
Page 298: ...App 6 APPENDICES Appendix 1 External Dimensions ...
Page 302: ...App 10 APPENDICES Appendix 3 Transportation Precautions ...
Page 306: ...REVISIONS 2 ...
Page 309: ......
Page 310: ......