115
3
NOTE
• Set 65535 (HFFFF) as a parameter value "9999".
• For the instruction codes HFF and HF3, their values are held once written but cleared to zero when the converter reset or All
parameter clear is performed.
[Special monitor selection No.]
Refer to
for details of the monitor items.
∗1
Input terminal monitor details ("1" denotes terminal ON and "2" denotes terminal OFF.)
∗2
Output terminal monitor details ("1" denotes terminal ON and "2" denotes terminal OFF.)
∗3
Absolute (unsigned) values are displayed.
[Fault data]
Refer to
for details of faults.
6
Parameter setting
Read H00 to H63 Refer to the instruction code list (on
) to read/write parameter
settings as required.
For the setting of
Pr.100
or later, the link parameter extended setting is
required.
4 digits
(B and E/D)
7
Write H80 to HE3
4 digits
(A and C/D)
8
Link parameter
extended setting
Read
H7F
Parameter settings are switched (extended) according to a setting from
H00 to H09.
For details of the settings, refer to the extended code in the instruction
code list (on
).
2 digits
(B and E1/D)
Write
HFF
2 digits
(A1 and C/D)
9
Product
profile
Model
Read
H7C
The model name can be read in ASCII code.
"H20" (blank code) is set for blank area.
Example) "FR-XC":
H46, H52, H2D, H58, H43, H20, ..., H20
20 digits
(B and E3/D)
Capacity
Read
H7D
The converter capacity can be read in ASCII code.
Data read is displayed in increments of 0.1 kW ( rounded down to one
decimal place).
"H20" (blank code) is set for blank area.
Example) 7.5K: H20, H20, H20, H20, H37,H35)
6 digits
(B and E2/D)
No.
Item
Read/
write
Instruction
code
Data description
Number of
data digits
(format)
Refer to
page 106
for data formats (A, A1, B, B1, C, D, E, E1, and F).
Data
Description
Increment
H01
Input current
0.01 A
H02
Input voltage
0.1 V
H03
Bus voltage
0.1 V
H05
Power supply
frequency
0.01 Hz
H06
Electronic thermal O/L
relay load factor
0.1%
H07
Input power
0.01 kW
H08
Cumulative power
1 kWh
H09
Cumulative
energization time
1 h
H0A
Input power with
regenerative driving
indication
0.01 kW
H0F
Input terminal status
⎯
H10
Output terminal status
⎯
Data
Description
Increment
H1C
Electricity cost
1
Data
Description
Increment
b15
b0
0
0
0
0
0
0
LOH
0
SOF
0
RES
0
0
0
0
0
b15
b0
RYB
RSO
RYA
0
0
0
ABC
0
0
0
0
0
0
0
0
0
When data read is H30B1
(The second latest fault: E.T)
(The latest fault: E.J)
0
1
0
1 0 0 0 0
0
1
1
0
0
0
1
1
b15
b8 b7
b0
The latest fault
(HB1)
The second latest fault
(H30)
Fault monitor details (example of the instruction code H74)
Data
Descript
ion
H00
No fault
H13
E.A
H23
E.B
H30
E.C
H40
E.D
H50
E.E
H51
E.F
H52
E.G
H90
E.H
HA1
E.Q
HA4
E.6
HB0
E.P
HB1
E.J
HB2
E.K
HB3
E.P
HC0
E.L
HC2
E.M
HC5
E.N
Data
Descript
ion
HF1
E.1
HFD
E.L
HB8
E.T
HB9
E.U
HBA
E.V
HBB
E.W
HF8
E.8
Data
Descript
ion