Main circuit terminal specification
45
2
∗3
For the FR-XC-15K or lower, it is the gauge of a cable with the continuous maximum permissible temperature of 70°C (PVC cable). It assumes
a surrounding air temperature of 40°C or less and the wiring distance of 20 m or less from the power supply to the converter.
For the FR-XC-22K / FR-XC-18.5K-PWM or higher, it is the gauge of a cable with the continuous maximum permissible temperature of 90°C
(PVC cable). It assumes a surrounding air temperature of 40°C or less and the wiring distance of 20 m or less from the power supply to the
converter.
(Selection example mainly for use in Europe.)
∗4
If a cable thinner than the recommended cable size is used, it may not be protected by the DC fuse. (Refer to
• 400 V class
∗1
It is the gauge of a cable with the continuous maximum permissible temperature of 75°C (HIV cable (600 V grade heat-resistant PVC insulated
wire), etc.). It assumes a surrounding air temperature of 50°C or less (40°C or less for the 40°C rating) and the wiring distance of 20 m or less
from the power supply to the converter.
∗2
The cable size is that of the THHW cable with continuous maximum permissible temperature of 75°C. It assumes a surrounding air temperature
of 40°C or less and the wiring distance of 20 m or less from the power supply to the converter.
(For the use in the United States or Canada, refer to
.)
∗3
For the FR-XC-15K or lower, it is the gauge of a cable with the continuous maximum permissible temperature of 70°C (PVC cable). It assumes
a surrounding air temperature of 40°C or less and the wiring distance of 20 m or less from the power supply to the converter.
For the FR-XC-22K / FR-XC-18.5K-PWM or higher, it is the gauge of a cable with the continuous maximum permissible temperature of 90°C
(PVC cable). It assumes a surrounding air temperature of 40°C or less and the wiring distance of 20 m or less from the power supply to the
converter.
(Selection example mainly for use in Europe.)
∗4
If a cable thinner than the recommended cable size is used, it may not be protected by the DC fuse. (Refer to
Model
Rating
Crimp terminal (for HIV cables, etc.)
Model
Rating
Crimp terminal
(for HIV cables, etc.)
R, S, T
R2, S2, T2
P, N
R1, S1
Earth
(ground)
R, S, T, R2, S2, T2
FR-XC-H7.5K
50°C
1.25-4
3.5-5
3.5-6
1.25-4
3.5-4
FR-XCL-H7.5K
50°C
3.5-5
40°C
40°C
FR-XC-H11K
50°C
1.25-4
5.5-5
5.5-6
1.25-4
5.5-5
FR-XCL-H11K
50°C
5.5-5
40°C
40°C
FR-XC-H15K
50°C
1.25-4
8-5
8-6
1.25-4
5.5-5
FR-XCL-H15K
50°C
8-5
40°C
40°C
FR-XC-H22K
FR-XC-H18.5K-PWM
50°C
1.25-4
14-8
22-6
1.25-4
14-6
FR-XCL-H22K
50°C
14-6
40°C
40°C
FR-XC-H30K
FR-XC-H22K-PWM
50°C
1.25-4
22-8
22-6
1.25-4
14-6
FR-XCL-H30K
50°C
22-6
40°C
40°C
FR-XC-H37K
FR-XC-H37K-PWM
50°C
1.25-4
38-8
38-8
1.25-4
14-8
FR-XCL-H37K
50°C
38-8
40°C
40°C
FR-XC-H55K
FR-XC-H55K-PWM
50°C
1.25-4
60-8
60-8
1.25-4
22-8
FR-XCL-H55K
50°C
60-8
40°C
40°C
Model
Rating
Cable gauge
HIV cables, etc. (mm
2
AWG/MCM
PVC cables, etc. (mm
2
)
Location in the
connection diagram
Earth
(ground)
Location in the
connection diagram
Location in the
connection diagram
Earth
(ground)
a, b
d
a, b
c
d
a, b
c
d
FR-XC-H7.5K
50°C
3.5
3.5
1.25
3.5
12
12
16
4
4
1.5
4
40°C
FR-XC-H11K
50°C
5.5
5.5
1.25
5.5
10
10
16
6
6
1.5
6
40°C
FR-XC-H15K
50°C
8
8
1.25
5.5
8
8
16
10
10
1.5
10
40°C
FR-XC-H22K
FR-XC-H18.5K-PWM
50°C
14
22
1.25
14
6
6
16
10
16
1.5
16
40°C
FR-XC-H30K
FR-XC-H22K-PWM
50°C
22
22
1.25
14
4
4
16
16
25
1.5
16
40°C
25
FR-XC-H37K
FR-XC-H37K-PWM
50°C
38
38
1.25
14
4
2
16
25
35
1.5
16
40°C
2
35
FR-XC-H55K
FR-XC-H55K-PWM
50°C
60
60
1.25
22
2
2
16
35
35
1.5
16
40°C
1
50
25