Installation of the converter and enclosure design
35
2
Mount point change of installation frame from the rear to the front
The upper and lower installation frames are attached on the multifunction regeneration converter (one for each position).
Change the mount point of the upper and lower installation frames from the rear to the front as shown in the figure.
When reattaching the installation frames, make sure that the installation orientation is correct.
Installation of the multifunction regeneration converter on the enclosure
Push the multifunction regeneration converter heat sink part outside the enclosure, and fix the multifunction regeneration
converter to the panel with upper and lower installation frames.
NOTE
• As the heat sink part protruded through the panel includes a cooling fan, this type of installation is not suitable for the
environment of water drops, oil, mist, dust, etc.
• Be careful not to drop screws, dust etc. into the multifunction regeneration converter and cooling fan section.
Shift
Upper
installation
frame
Shift
Lower
installation
frame
Inside the
enclosure
Enclosure
Exhausted air
Converter
Cooling
wind
∗1
Installation
frame
10 mm
∗2
∗1
Dimension of the outside of the enclosure
∗2
To avoid interference with the cooling fan on top of the heatsink, the thickness of the rear
panel of the enclosure should not exceed 10 mm and the space around the fan should be
cleared.
Multifunction regeneration
converter
Dimension of the
outside of the
enclosure (mm)
FR-XC-(H)37K, FR-XC-H55K
FR-XC-(H)37K-PWM, FR-XC-H55K-PWM
105
FR-XC-55K
FR-XC-55K-PWM
135