Rating
158
6.1.2
FR-XC-[ ]K-PWM
200 V class
∗1
The harmonic suppression function in this model is enabled initially.
∗2
The converter with its harmonic suppression function disabled can be set in the power regeneration mode.
∗3
Selection example for 220 V power supply voltage.
∗4
IP20 for the FR-XCB.
∗5
The DC bus voltage is approx. 297 VDC at an input voltage of 200 VAC, approx. 327 VDC at 220 VAC, and approx. 342 VDC at 230 VAC.
∗6
One inverter for operation in the power regeneration mode.
∗7
Mass of the FR-XC alone.
∗8
Maximum capacity of regenerative power generated from the Mitsubishi Electric 4-pole standard motor in each axis.
Model FR-XC-[ ]K-PWM
18.5
22
37
55
Harmonic suppression
Common bus regeneration mode
50°C ra
tin
g
Applicable inverter
capacity (kW)
Disabled
22
30
37
55
Enabled
18.5
22
37
55
Applicable motor
current (A)
Disabled
90
115
145
215
Enabled
76
90
145
215
Rated input current (A)
Disabled
Power
driving
92
124
151
223
Regenerative
driving
74
102
125
186
Enabled
(HS)
Power/
regenerative
driving
69
82
134
198
Overload current rating
100% continuous / 150% 60 s
Power supply capacity
(kVA)
Disabled
41
52
66
100
Enabled
30
35
57
84
40
°C
r
atin
g
Applicable inverter
capacity (kW)
Disabled
22
30
37
55
Enabled
18.5
22
37
55
Applicable motor
current (A)
Disabled
99
127
160
236
Enabled
83
99
160
236
Rated input current (A)
Disabled
Power
driving
101
136
166
245
Regenerative
driving
81
112
138
204
Enabled
(HS)
Power/
regenerative
driving
75
90
147
217
Overload current rating
100% continuous / 150% 60 s
Power supply capacity
(kVA)
Disabled
45
57
73
110
Enabled
32
38
62
92
Power regenera
tion mode
50
°C r
atin
g Potential regenerative capacity (kW)
18.5
22
30
45
Rated current (A) (regenerative driving)
62
74
102
152
Overload current rating
100% continuous / 150% 60 s
40
°C r
atin
g Potential regenerative capacity (kW)
18.5
22
30
45
Rated current (A) (regenerative driving)
68
81
112
167
Overload current rating
100% continuous / 150% 60 s
Po
we
r sou
rce
Rated input AC voltage/
frequency
Disabled
Three-phase 200 to 240 V, 50/60 Hz
Enabled
Three-phase 200 to 230 V, 50/60 Hz
Permissible AC voltage
fluctuation
Disabled
Three-phase 170 to 264 V, 50/60 Hz
Enabled
Three-phase 170 to 253 V, 50/60 Hz
Permissible frequency
fluctuation
Disabled
±5%
Enabled
±5%
Input power factor
Enabled
0.99 or more (when load ratio is 100%)
Protection rating of structure (IEC 60529)
Cooling system
Forced air
Number of connectable inverters
Approx. mass (kg)
10.5
10.5
28
38