Parameter list
84
3.4
Parameter list
NOTE
•
indicates simple mode parameters.
• The setting of parameters in highly colored cell (
) is changeable during operation even if "1" (write disabled) is set to
Pr.77 Parameter write selection
.
Parameter read/write requires the operation panel (FR-DU08) or the optional parameter unit (FR-PU07 or FR-
PU07BB(-L)).
Pr.
Name
Setting range
Minimum
setting
increment
Initial value
Refer to
page
Customer
setting
0
Simple mode selection
0, 9999
0
0
1
Maximum power supply
frequency
60 Hz (Read only)
—
(60 Hz)
2
Minimum power supply
frequency
50 Hz (Read only)
—
(50 Hz)
3
LOH terminal function
selection
0, 3 to 5, 9999
1
5
4
SOF terminal function
selection
1
0
7
RES terminal function
selection
1
3
8
SOF input selection
0 to 2
1
0
9
OH input selection
0, 1
1
0
11
RSO terminal function
selection
0 to 4, 6 to 11, 14 to 18, 98,
99, 101 to 104,106 to 111,
114 to 118, 198, 199, 9999
1
1
12
RYA terminal function
selection
1
0
16
ABC terminal function
selection
1
99
22
Current limit level
0 to 190%
0.1%
150
23
Current limit level
(regenerative)
0 to 190%, 9999
0.1%
9999
31
Life alarm status display
0, 1, 4, 5, 8, 9, 12, 13 (Read
only)
1
0
32
Inrush current limit circuit life
display
0 to 100% (Read only)
1%
100%
33
Control circuit capacitor life
display
0 to 100% (Read only)
1%
100%
34
Maintenance timer
0 (1 to 9998)
1
0
35
Maintenance timer warning
output set time
0 to 9998, 9999
1
9999
44
Instantaneous power failure
detection signal clear
0, 9999
1
9999
46
Watt-hour meter clear
0, 10, 9999
1
9999
47
Energization time carrying-
over times
Read only
1
0
48
Cumulative power monitor
digit shifted times
0 to 4, 9999
1
9999
52
PU main monitor selection
0, 5 to 10, 25, 28
1
0
57
Restart selection
0, 9999
1
9999
58
Free parameter 1
0 to 9999
1
9999
59
Free parameter 2
0 to 9999
1
9999
61
Key lock operation selection
0, 10
1
0
65
Retry selection
0 to 4
1
0
67
Number of retries at fault
occurrence
0 to 10, 101 to 110,
1001 to 1010, 1101 to 1110
1
0
68
Retry waiting time
0.1 to 600 s
0.1 s
1 s
69
Retry count display erase
0
1
0
Summary of Contents for FR-XC-11K
Page 75: ...MEMO 74 ...
Page 131: ...MEMO 130 ...
Page 155: ...MEMO 154 ...
Page 173: ...MEMO 172 ...