Precautions for selecting peripheral devices
22
Power regeneration mode
• 200 V class
• 400 V class
∗1
Manufacturer: Mersen Japan KK
Contact: Sun-Wa Technos Corporation
NOTE
• Install fuses across terminals P/+ and P/+, and across terminals N/- and N/- of the multifunction regeneration converter and
the inverter.
[Estimated lifespan of fuses]
∗1
Estimated lifespan for when the yearly average surrounding air temperature is 50°C. (without corrosive gas, flammable gas, oil mist, dust and
dirt etc.)
NOTE
• If the fuse melts down, wiring failure such as a short circuit may be the cause. Find out the cause and remove it before
replacing the fuse.
FR-XC series
converter
capacity (kW)
Fuse rating (A)
Model
Fuse holder (2 poles)
FR-XC-7.5K
125
6.9 URD 30 TTF 0125
—
FR-XC-11K
160
6.9 URD 30 TTF 0160
—
FR-XC-15K
200
6.9 URD 30 TTF 0200
—
FR-XC-22K
FR-XC-18.5K-PWM
315
6.9 URD 30 TTF 0315
—
FR-XC-30K
FR-XC-22K-PWM
400
6.9 URD 30 TTF 0400
—
FR-XC-37K
FR-XC-37K-PWM
500
6.9 URD 30 TTF 0500
—
FR-XC-55K
FR-XC-55K-PWM
700
6.9 URD 31 TTF 0700
—
FR-XC series
converter capacity
(kW)
Fuse rating (A)
Model
Fuse holder (2 poles)
FR-XC-H7.5K
50
6.9 URD 30 TTF 0050
—
FR-XC-H11K
80
6.9 URD 30 TTF 0080
—
FR-XC-H15K
125
6.9 URD 30 TTF 0125
—
FR-XC-H22K
FR-XC-H18.5K-PWM
160
6.9 URD 30 TTF 0160
—
FR-XC-H30K
FR-XC-H22K-PWM
200
6.9 URD 30 TTF 0200
—
FR-XC-H37K
FR-XC-H37K-PWM
250
6.9 URD 30 TTF 0250
—
FR-XC-H55K
FR-XC-H55K-PWM
350
6.9 URD 30 TTF 0350
—
Components
Estimated lifespan
Replacement method
Fuse
10 years
Replace by new one