Wiring
62
2.8.3
Wiring (power regeneration mode)
Wiring between the power supply and the reactor
• Cable gauge differs by the capacity. Select an appropriate cable by referring to
to perform wiring.
∗1
Select a MCCB and a MC according to the inverter capacity.
∗2
For selection of MCCB for the converter, refer to
Wiring between the reactor and the converter
• Cable gauge differs by the capacity. Select an appropriate cable by referring to
to perform wiring.
Wiring between the converter and the inverter
• For the cable gauge of the cable for the main circuit terminals P/+ and N/- (P to P and N to N), refer to
NOTE
• Connecting opposite polarity of terminals P4 and N/- will damage the converter.
MCCB
∗1
MC
∗1
Dedicated reactor
(FR-XCL)
R/L1
S/L2
T/L3
R2/L12
S2/L22
T2/L32
R/L1
S/L2
T/L3
Power
supply
To inverter
MCCB
∗2
AC reactor
(FR-HAL)
Multifunction regeneration
converter
Dedicated reactor
(FR-XCL)
R/L1
S/L2
T/L3
R2/L12
S2/L22
T3/L32
P/+
N/-
R2/L12
S2/L22
T3/L32
Total wiring length
10 m or shorter
Multifunction regeneration
converter
Inverter
P/+
N/-
P4
P/+
R2/L12
S2/L22
T2/L32
∗2
N/-
∗1
R/L1
S/L2
T/L3
∗1
Installation of a fuse on each cable is recommended to prevent the damage from
spreading in case of an inverter failure. Select the fuse according to the motor capacity.
To use a motor whose capacity is smaller than the inverter capacity by two ranks or
more, select the fuse with the capacity that is one rank lower than the inverter capacity.
Refer to the fuse selection table on
.
∗2
Do not install any MCCB between the inverter and the converter (P to P and N to N).
Main circuit wiring length
5 m or shorter