60
Class 0x01 Instance 1
[Attribute]
The value indicates that the option is connected to the FR-A800 series.
The value indicates that the option is connected to the FR-F800 series.
High byte of hexadecimal word data means integer, and low byte means decimal.
For example, when the read data is 0x010A, it means version 1.010.
Bit definition
Bit 0: 0 = allocated, 1 = not allocated, Bit 2: always 0, Bit 8: 1 = alarm occurrence, Bit 9: always 0, Bit 10: 1 = LED is flickering red, Bit 11:
1 = LED is lit red
The actual data are 0x04, 0x41, 0x38, 0x30, 0x30 when the option is connected to the FR-A800 series.
The actual data are 0x04, 0x46, 0x38, 0x30, 0x30 when the option is connected to the FR-F800 series.
0x04 means 4 byte data, and the rest means ASCII code of "A800"/"F800".
[Service]
As set in
Pr. 75
. Refer to the Instruction Manual (Detailed) of the inverter for details of
Pr. 75
.
If the inverter does not accept the command, neither inverter reset nor all parameter clear will be performed.
Class 0x01 Instance 1
Attribute ID
Access
Definition
Data type
No. of
data bytes
Attribute value
1
Get
Vendor ID (Mitsubishi electric)
UINT
2
161
2
Get
Device Type (AC drive)
UINT
2
02
3
Get
Product Code
UINT
2
71
, 73
4
Get
Revision
STRUCT
2
1.YYY
5
Get
Status
WORD
2
6
Get
Serial Number
UDINT
4
xxxxxxxx
7
Get
Product Name(FR-A800/F800)
SHORT_STRING
5
A800/F800
Service code
Symbol
Name
Setting range
Description
0x05
Reset
Reset
0
Inverter reset
1
Inverter reset after all parameter clear
0x0E
Get
Get_Attribute_Single
—
Get Attribute Single