24
4.2.1
DeviceNet address (Pr. 345)
The definition of
Pr. 345
is as follows.
To enable the device node address of bit 0 to 5, set the node address switches to "64 or higher". (Refer to
For an error reset via DeviceNet communication, the communication continues.
When operating the inverter through the DeviceNet communication, set
Pr.340
0 in advance to enable the inverter to run in the NET
operation mode after the inverter reset.
Pr.
Name
Setting range
Minimum setting
increments
Initial
value
345
DeviceNet address
0 to 4095
1
63
Bit
Item
Initial
value
Setting
range
Definition
0 to 5
Device Node Address
63
0 to 63
Node Address (MAC ID) of device is
set between 0 and 63.
Node address can be set with
DeviceNet Object Class 0x03,
Instance1, Attribute1.
(Refer to
11
Selection of continuous
communication at
inverter reset (ResCom)
0
0
Reset the option unit in synchronization with the inverter.
When connection is timed out, communication may not resume according to
the master action. In this case, release connection and reestablish to make
communication enabled.
1
The option unit will not be reset even if the inverter is reset and communication
continues.
After inverter reset, preset a value other than "0" in
Pr. 340
so that the inverter
starts in Network operation mode.
12 to 15
Reserved
0
0
Set "0" always. When a value other than "0" is set, the inverter operates as
when "63" (initial value) is set in
Pr. 345
.
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Reserved
Communication continuation selection (ResCom)
ResCom
Device Node Address
Reserved