Specifications of the FR-A5ND compatible mode
The table below shows the differences between the FR-A5ND compatible mode and the normal mode.
Refer to the FR-A5ND manuals for details of each function of compatible mode.
Class
ID
Instance
ID
Attribute
ID
Name
FR-A5ND
compatible mode
Normal mode
(FR-A8ND)
Refer
to page
0x03
1
1
Node address setting (MAC ID)
The value can be written to
Pr.345
regardless of the set
values of the node address
switches.
The value cannot be written
to
Pr.345
when "0 to 63" is
set for the node address
switches.
0x03
1
3
Bus-off interrupt
─
0x03
1
4
Bus-off counter
0x28
1
6
Rated current
(Pr.9)
0.01 A/0.1 A increments
0.1 A increments
0x28
1
7
Rated voltage
Read from/write to
Pr.83
Read from/write to
Pr.19
0.1 V increments
1 V increments
0x28
1
8
Motor capacity
(Pr.80)
─
0x28
1
9
Rated frequency
(Pr.84)
0x28
1
12
Number of motor poles
(Pr.144)
0x28
1
15
Base speed
(Pr.3)
0x29
1
5
NetCtrl (operation command
source)
The value can be written
during inverter running.
When the operation
command source is set to
communication, the values
cannot be written while the
inverter is running.
0x29
1
16
DeviceNet error mode
─
0x29
1
40
Input assembly
(
: Available,
: Not available)