57
7
• Input Instance 177 details
Byte0
Bit0
Running Fwd
Forward rotation
(0: other than forward rotation 1: forward rotation)
Bit1
Running Rev
Reverse rotation
(0: other than reverse rotation 1: reverse rotation)
Bit2
Faulted
Inverter fault signal
(0: inverter is under normal operation 1: inverter is in a fault state)
Bit3
Run command
mode
0: Command is disabled in network operation
1: Command is enabled in network operation
Bit4
Terminal RUN
Terminal RUN (0: OFF 1: ON)
Bit5
Terminal SU
Terminal SU (0: OFF 1: ON)
Bit6
Terminal IPF
Terminal IPF (0: OFF 1: ON)
Bit7
Terminal OL
TerminalOL (0: OFF 1: ON)
Byte1
Bit0
Terminal FU (0: OFF 1: ON)
Bit1
Terminal ABC1
Terminal ABC1 (0: OFF 1: ON)
Bit2
Terminal ABC2
Terminal ABC2 (0: OFF 1: ON)
Bit6
Hz
0: The increment of 1 r/min is used for Byte2 and Byte3.
1: The increment of 0.01 Hz is used for Byte2 and Byte3.
Bit7
32Bit format
0: The format for 16-bit data is being selected.
1: The format for 32-bit data is being selected.