51
7
Input Instance 176 (inverter
→
master)
When Input Instance 176 is used, 16 bits parameter data is provided.
When using Input Instance 176, set Output Instance to 126.
• Input Instance 176 details
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
AtReference
Ref From Net
Ctrl From Net
Ready
Running
Rev
Running
Fwd
Run
command
mode
Faulted
1
PrEnd
Reserved (0)
2
Speed actual (low byte)
3
Speed actual (high byte)
4
Parameter read data (low byte)
5
Parameter read data (high byte)
Byte0
Bit0
Faulted
Inverter fault signal
(0: inverter is under normal operation 1: inverter is in a fault state)
Bit1
Run Command
0: Command is disabled in network operation
1: Command is enabled in network operation
Bit2
Running Fwd
Forward rotation (0: other than forward rotation 1: forward rotation)
Bit3
Running Rev
Reverse rotation (0: other than reverse rotation 1: reverse rotation)
Bit4
Ready
Ready signal (0: operation preparation 1: operation ready)
Always "1" after power ON
Bit5
CtrlFromNet
0: The inverter is set not to accept the commands Bit0 and Bit1 of Byte0.
1: The inverter is set to accept the commands Bit0 and Bit1 of Byte0.
Bit6
RefFromNet
0: The inverter is set not to accept the speed commands.
1: The inverter is set to accept the speed commands.
Bit7
AtReference
Up-to-frequency signal (SU signal)
(Same definition with Class 0x2A Instance 1 Attribute 3. Refer to