49
7
7.1.3
Output Instance 126/Input Instance 176
Output instance 126 (master
→
inverter)
When using Output Instance 126, set Input Instance to 176.
• Output Instance 126 details
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Write Attr
Net Ref
Net Ctrl
Reserved (0)
Reserved (0)
Fault Reset
Run Rev
Run Fwd
1
Parameter Instance ID
2
Speed reference or parameter write data (low byte)
3
Speed reference or parameter write data (high byte)
4
Parameter class ID
5
Parameter attribute ID
Byte0
Bit0
Run Fwd
Forward rotation signal (0: forward rotation OFF 1: forward rotation ON)
Only NetCtrl (Bit 5) = 1
is valid.
Bit1
Run Rev
Reverse rotation signal (0: reverse rotation OFF 1: reverse rotation ON)
Bit2
Fault Reset
Reset request at an error occurrence
Valid only at in inverter trip
(0: no function 1: fault reset request)
Bit5
NetCtrl
0: The values set in Bit0 to 2 of Byte0 are not written to the inverter.
1: The values set in Bit0 to 2 of Byte0 are written to the inverter.
Bit6
NetRef
0: The speed reference is not written to the inverter.
1: The speed reference is written to the inverter.
Bit7 Write Attr
0: Byte2 and Byte3 are set to the speed reference.
1: Byte2 and Byte3 are set to the value to be written to the attribute.