Troubleshooting ]
- 125 -
HWE07150
GB
1. Error
Code
ACCT sensor fault (Detail code 115)
2. Error
definition and error detection method
When the formula "output current < 1.5 Arms" remains satisfied for 10 seconds while the inverter is in operation.
3. Cause, check method and remedy
Refer to section - 6 -"Inverter" under part [4] "Trouble shootiong principal parts" for error codes related to the
inverter.(page 172)
1. Error
Code
ACCT sensor circuit fault (Detail code 117)
2. Error
definition and error detection method
When an error value is detected with the ACCT detection circuit just before the inverter starts
3. Cause, check method and remedy
Refer to section - 6 -"Inverter" under part [4] "Trouble shootiong principal parts" for error codes related to the
inverter.(page 172)
5301
Cause
Check method and remedy
(1)
Inverter open output phase
Check the output wiring connections.
(2)
Compressor failure
Refer to
X
[4]-6-(2)[2].(page 174)
(3)
INV board failure
Refer to
X
[4]-6-(2)[1], [3], [4].(page 174)
5301
Cause
Check method and remedy
(1)
INV board failure
Refer to
X
[4]-6-(2) [1], [3], [4].(page 174)
(2)
Compressor failure
Refer to
X
[4]-6-(2) [2].(page 174)
Summary of Contents for City Multi PFAV-P500VMH-E
Page 1: ......
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 37: ... 28 ...
Page 39: ... 30 ...
Page 49: ... 40 ...
Page 55: ... 46 ...
Page 59: ... 50 ...
Page 61: ... 52 ...
Page 65: ... 56 ...
Page 67: ... 58 ...
Page 73: ... 64 ...
Page 75: ... 66 ...
Page 95: ... 86 ...
Page 107: ... 98 ...
Page 195: ... X Troubleshooting 186 HWE07150 GB ...
Page 197: ... 188 ...
Page 242: ......