X
Troubleshooting ]
- 149 -
HWE07150
GB
1. Error
Code
Function setting error
2. Error source, cause, check method and remedy
1. Error
Code
Model setting error
2. Error source, cause, check method and remedy
1. Error
Code
Incompatible unit combination
2. Error
definition and error detection method
The check code will appear when the indoor units with different refrigerant systems are connected.
3. Error source, cause, check method and remedy
7113
Error source
Cause
Check method and remedy
Outdoor unit
(1)
Wiring failure
1)
Control board connector
Check the CNTYP2,4,5 connector connection.
INV board connector
Check the CNTYP connector connection(P300 - P450
models only)
(2)
Disconnected connector, short cir-
cuit, contact failure
2)
Check the compatibility of the circuit board, and replace
it with a correct one if necessary.
(3)
Incompatibility between the control
board and INV board (Replacement
of the circuit board with the wrong
one)
3)
Check the model selection switch on the outdoor unit
(Dipswitch SW5-7 on the control board.).
7117
Error source
Cause
Check method and remedy
Outdoor unit
(1)
Wiring failure
1)
Control board connector
Check the CNTYP2,4,5 connector connec-
tion.
INV board connection
Check the CNTYP connector connection
(P300 - P450 models only)
(2)
Disconnected connector, short circuit, contact
failure
7130
Error source
Cause
Check method and remedy
Outdoor unit
The connected indoor unit is for use with R22
or R407C. Incorrect type of indoor units are
connected.
The M-NET connection adapter is connected
to the indoor unit system in a system in which
the Slim Model (A control) of units are con-
nected to the M-NET.
Check the connected indoor unit model.
Check whether the connecting adapter for
M-NET is not connected to the indoor unit.
(Connect the connecting adapter for M-NET
to the outdoor unit.)
Summary of Contents for City Multi PFAV-P500VMH-E
Page 1: ......
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 37: ... 28 ...
Page 39: ... 30 ...
Page 49: ... 40 ...
Page 55: ... 46 ...
Page 59: ... 50 ...
Page 61: ... 52 ...
Page 65: ... 56 ...
Page 67: ... 58 ...
Page 73: ... 64 ...
Page 75: ... 66 ...
Page 95: ... 86 ...
Page 107: ... 98 ...
Page 195: ... X Troubleshooting 186 HWE07150 GB ...
Page 197: ... 188 ...
Page 242: ......