1. Error
Code
Discharge temperature fault
2. Error
definition and error detection method
1) If the discharge temperature of 120 °C [248°F] or more is detected during the above operation (the first detection), the outdoor
unit stops once, turns to anti-restart mode for 3 minutes, and restarts after 3 minutes automatically.
2) If the discharge temperature of 120° C [248°F] or more is detected again (the second detection) within 30 minutes after the
second stop of the outdoor unit described above, the mode will be changed to 3 - minute restart mode, then the outdoor unit
will restart in 3 minutes.
3) If the discharge temperature of 120°C [248°F] or more is detected (the third detection) within 30 minutes after the stop of the
outdoor unit described above (regardless of the first or the second stop), the outdoor unit will make an error stop, and the error
code "1102" will be displayed.
4) If the discharge temperature of 120°C [248°F] or more is detected more than 30 minutes after the previous stop of the outdoor
unit, the detection is regarded as the first detection, and the operation described in step 1 above will start.
5) For 30 minutes after the stop (the first stop or the second stop) of the outdoor unit, preliminary errors will be displayed on the
LED display.
3. Cause, check method and remedy
1102
Cause
Check method and remedy
(1)
Gas leak, gas shortage
Refer to the page on refrigerant amount evaluation.(page 89)
(2)
Overload operation
Check operating conditions and operation status of indoor/
outdoor units.
(3)
LEV failure on the indoor unit
Perform a cooling or heating operation to check the opera-
tion.
Cooling: Indoor unit LEV
LEV1
LEV2a,b
Heating: Indoor unit LEV
LEV2a,b
Refer to the section on troubleshooting the LEV.(page 166)
(4)
Outdoor unit LEV1 actuation failure
Outdoor unit LEV2a, b actuation failure
(5)
Closed refrigerant service valve
Confirm that the refrigerant service valve is fully open.
(6)
Outdoor fan (including fan parts) failure, mo-
tor failure, or fan controller malfunction
Rise in discharge temp. by low pressure
drawing for (3) - (6).
Check the fan on the outdoor unit.
Refer to the section on troubleshooting the outdoor unit
fan.(page 165)
(7)
Gas leak between low and high pressures
(4-way valve failure, Compressor failure, So-
lenoid valve (SV1a) failure)
Perform a cooling or heating operation and check the opera-
tion.
(8)
Thermistor failure
(TH4)
Check the thermistor resistor.(page 123)
(9)
Input circuit failure on the controller board
thermistor
Check the inlet air temperature on the LED monitor.
Summary of Contents for City Multi PFAV-P500VMH-E
Page 1: ......
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 37: ... 28 ...
Page 39: ... 30 ...
Page 49: ... 40 ...
Page 55: ... 46 ...
Page 59: ... 50 ...
Page 61: ... 52 ...
Page 65: ... 56 ...
Page 67: ... 58 ...
Page 73: ... 64 ...
Page 75: ... 66 ...
Page 95: ... 86 ...
Page 107: ... 98 ...
Page 195: ... X Troubleshooting 186 HWE07150 GB ...
Page 197: ... 188 ...
Page 242: ......