IX
Test Run Mode ]
- 91 -
HWE07150
GB
(2) Example: Outdoor unit PUHY-P500YSHM-A, Indoor unit PFAV-P500VMH-E
(3) Sample calculation
CAUTION
Charge liquid refrigerant (as opposed to gaseous refrigerant) into the system.
If gaseous refrigerant is charged into the system, the composition of the refrigerant in the cylinder will change and may
result in performance loss.
15.88[3/4"]
(30m)[98 ft]
9.52[3/8"]
(1m)[3 ft]
9.52[3/8"]
(3m)[9 ft]
Liquid
separetor
Indoor
All the pipes in the figure are liquid pipes.
15.88 : 30 m
9.52 : 3 m + 1m = 4 m
According to the above formula
The calculation result would be 11.24, and it is rounded up to the nearest 0.1.
The final result will be as follows:
Amount of refrigerant to be charged (kg) = (0.2 X 30) + (0.06 X 4) + 5.0 = 11.24 kg
Amount of refrigerant to be charged = 11.3 kg
All the pipes in the figure are liquid pipes.
[3/4"] : [98 ft]
[3/8"] : [9 ft] + [3 ft] = [12 ft]
According to the above formula
The calculation result would be 395.5 oz, and it is rounded up to the nearest 1 oz.
The final result will be as follows:
Amount of refrigerant to be charged (oz) = (2.15 X 98) + (0.65 X 12) + 177 = 395.5 oz
Amount of refrigerant to be charged = 396 oz
Summary of Contents for City Multi PFAV-P500VMH-E
Page 1: ......
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 37: ... 28 ...
Page 39: ... 30 ...
Page 49: ... 40 ...
Page 55: ... 46 ...
Page 59: ... 50 ...
Page 61: ... 52 ...
Page 65: ... 56 ...
Page 67: ... 58 ...
Page 73: ... 64 ...
Page 75: ... 66 ...
Page 95: ... 86 ...
Page 107: ... 98 ...
Page 195: ... X Troubleshooting 186 HWE07150 GB ...
Page 197: ... 188 ...
Page 242: ......