X
Troubleshooting ]
- 120 -
HWE07150
GB
1. Error
Code
Instantaneous overcurrent (Detail code 106)
Overcurrent (Detail code 107)
2. Error
definition and error detection method
P200 and P250 models
Overcurrent 94 Apeak or 22 Arms and above is detected by the current sensor.
P300 models and above
Overcurrent 94 Apeak or 35 Arms and above is detected by the current sensor.
3. Cause, check method and remedy
Refer to section - 6 - "Inverter" under part [4] "Trouble shooting principal parts" for error codes related to the
inverter.(page 172)
1. Error
Code
Short-circuited IPM/Ground fault (Detail code 104)
2. Error
definition and error detection method
When IPM/IGBT short damage or grounding on the load side is detected just before starting the inverter.
3. Cause, check method and remedy
In the case of 4250
In the case of 4255
Refer to section - 6 - "Inverter" under part [4] "Trouble shooting principal parts" for error codes related to the
inverter.(page 172)
4250
Cause
Check method and remedy
(1)
Inverter output related
Refer to
X
[4] - 6 - (2) [1] - [4].(page 174)
Check the IGBT module resistance value of the INV board, if no
problems are found.
(Refer to the Trouble shooting for IGBT module)
4250
4255
Cause
Check method and remedy
(1)
Grounding fault compressor
Refer to
X
[4] - 6 - (2) [2].(page 174)
(2)
Inverter output related
Refer to
X
[4] - 6 - (2) [1]- [4].(page 174)
Cause
Check method and remedy
(1)
Grounding fault of fan motor
Refer to
X
[4] - 6 - (2) [5].(page 175)
(2)
Fan board failure
Refer to
X
[4] - 6 - (2) [6].(page 175)
Summary of Contents for City Multi PFAV-P500VMH-E
Page 1: ......
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 37: ... 28 ...
Page 39: ... 30 ...
Page 49: ... 40 ...
Page 55: ... 46 ...
Page 59: ... 50 ...
Page 61: ... 52 ...
Page 65: ... 56 ...
Page 67: ... 58 ...
Page 73: ... 64 ...
Page 75: ... 66 ...
Page 95: ... 86 ...
Page 107: ... 98 ...
Page 195: ... X Troubleshooting 186 HWE07150 GB ...
Page 197: ... 188 ...
Page 242: ......