II
Restrictions ]
- 19 -
HWE07150
GB
2. M-NET Address settings
(1) Address settings table
The need for address settings and the range of address setting depend on the configuration of the system.
*1. If an address is a duplicate of an indoor unit or outdoor unit of another refrigerant circuit, set another address, which
is within the setting range and is not in use.
*2. To set the outdoor unit address to "100," set the switches to "50."
*3. For the addresses of the outdoor units to be used together, set consecutive numbers in order from the one with the
highest capacity.
Furthermore, for the outdoor units of the same refrigerant circuit, the order of OC and OS becomes from the one with
the highest capacity. (If the capacity is the same, the order is from the one with the lowest address.)
Unit or controller
Symbol Address setting
range
Setting method
Facto-
ry set-
ting
Indoor unit
Main/sub unit
IC
01 to 50
*1
Assign the smallest address to the main indoor
unit in the group, and assign sequential address
numbers to the rest of the indoor units in the
same group.
00
LOSSNAY, OA processing unit
LC
01 to 50
*1
Assign an arbitrary but unique address to
each of these units after assigning an ad-
dress to all indoor units.
00
MA remote controller
MA
No address settings required. (The main/sub setting must be
made if 2 remote controllers are connected to the system.)
Main
Outdoor unit
OC
OS
51 to 100
*2
Assign an address that equals the lowest ad-
dress of the indoor units in the same refriger-
ant circuit plus 50.
Assign sequential addresses to the outdoor
units in the same refrigerant circuit. The out-
door units in the same refrigerant circuit are
automatically designated as OC and OS.
*3
00
System controller Group remote
controller
TR,
SC
0, 201 to 250
Assign an address that equals the sum of the
smallest group number of the group to be
controlled and 200.
201
System remote
controller
SR,
SC
Assign an arbitrary but unique address within
the range listed on the left to each unit.
ON/OFF re-
mote controller
AN,
SC
Assign an address that equals the sum of the
smallest group number of the group to be
controlled and 200.
Schedule timer
(compatible
with M-NET)
ST,
SC
Assign an arbitrary but unique address within
the range listed on the left to each unit.
202
Central con-
troller
G(B)-50A
GR,
SC
000,
201 to 250
Assign an arbitrary but unique address within
the range listed on the left to each unit.
000
LM adapter
SC
201 to 250
Assign an arbitrary but unique address within
the range listed on the left to each unit.
247
Summary of Contents for City Multi PFAV-P500VMH-E
Page 1: ......
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 37: ... 28 ...
Page 39: ... 30 ...
Page 49: ... 40 ...
Page 55: ... 46 ...
Page 59: ... 50 ...
Page 61: ... 52 ...
Page 65: ... 56 ...
Page 67: ... 58 ...
Page 73: ... 64 ...
Page 75: ... 66 ...
Page 95: ... 86 ...
Page 107: ... 98 ...
Page 195: ... X Troubleshooting 186 HWE07150 GB ...
Page 197: ... 188 ...
Page 242: ......