[
X
Troubleshooting ]
- 135 -
HWE07150
GB
1. Error
Code
No ACK error
2. Error
definition and error detection method
The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans-
mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.)
The address/attribute appeared on the display on the remote controller indicates the controller which did not provide
the response (ACK).
3. System
configuration
(3) System connected to the system controllers (MELANS)
6607
Error
source
address
Error display
Detection
method
Cause
Check method and remedy
Out-
door
unit
(OC)
M-NET remote
controller (RC)
System control-
ler (SC)
MA remote
controller (MA)
No acknowl-
edgement
(ACK) at IC
transmis-
sion to OC
Same cause as that for system with one
outdoor unit
Same remedy as that for
system with one outdoor
unit
Indoor
unit
(IC)
M-NET remote
controller (RC)
MA remote
controller (MA)
No acknowl-
edgement
(ACK) at RC
transmis-
sion to IC
Same as grouping of units in a system
with multiple outdoor units
Same remedy as that for
grouping of units in a sys-
tem with multiple outdoor
units
System control-
ler (SC)
No acknowl-
edgement
(ACK) at SC
transmis-
sion to IC
1.
Error occurrence on some IC
Same remedy as that for
system with one outdoor
unit
(1)
Same cause as that for system with one
outdoor unit
2.
Error occurrence on all IC in the system
with one outdoor unit
1) Check the LED display
for troubleshooting on the
outdoor unit.
(1)
Total capacity error (7100)
If an error is found,
check the check code
definition, and correct
the error.
If no error is found,
check 2).
(2)
Capacity code error (7101)
(3)
Error in the number of connected units
(7102)
(4)
Address setting error (7105)
(5)
Disconnection or short circuit of the trans-
mission line for the outdoor unit on the ter-
minal block for centralized control line
connection (TB7)
2) Check (5) - (7) on the left.
(6)
Turn off the power source of the outdoor
unit
(7)
Malfunction of electrical system for the
outdoor unit
3.
Error occurrence on all IC
Check voltage of the
transmission line for cen-
tralized control.
20V or more: Check (1)
and (2) on the left.
Less than 20V: Check
(3) on the left.
(1)
Same causes as (1) - (7) described in 2.
(2)
The male power supply connectors on 2
or more outdoor units are connected to
the female power supply switch connector
(CN40) for the transmission line for cen-
tralized control.
(3)
Disconnection or shutdown of the power
source of the power supply unit for trans-
mission line
(4)
System controller (MELANS) malfunction
Summary of Contents for City Multi PFAV-P500VMH-E
Page 1: ......
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 37: ... 28 ...
Page 39: ... 30 ...
Page 49: ... 40 ...
Page 55: ... 46 ...
Page 59: ... 50 ...
Page 61: ... 52 ...
Page 65: ... 56 ...
Page 67: ... 58 ...
Page 73: ... 64 ...
Page 75: ... 66 ...
Page 95: ... 86 ...
Page 107: ... 98 ...
Page 195: ... X Troubleshooting 186 HWE07150 GB ...
Page 197: ... 188 ...
Page 242: ......