X
Troubleshooting ]
- 144 -
HWE07150
GB
1. Error
Code
Total capacity error
2. Error
definition and error detection method
The model total of indoor units in the system with one outdoor unit exceeds limitations.
3. Error source, cause, check method and remedy,
Note1: Do not connect the indoor unit to an outdoor unit other than the PUHY-P500YSHM-A.
Note2: Be sure to connect the indoor unit and outdoor unit on a one-to-one basis.
7100
Error source
Cause
Check method and remedy
Outdoor unit
(1)
The model total of indoor units in the sys-
tem with one outdoor unit exceeds the fol-
lowing table.
1)
Check the model total (capacity code total) of in-
door units connected.
2)
Check the model name (capacity code) of the
connected indoor unit set by the switch (SW2 on
indoor unit board).
When the model name set by the switch is differ-
ent from that of the unit connected, turn off the
power source of the outdoor and the indoor units,
and change the setting of the model name (ca-
pacity code).
(2)
The model selection switches (SW5-1 - 5-
4) on the outdoor unit are set incorrectly.
Check the setting for the model selection switch
on the outdoor unit (Dipswitches SW5-1 - 5-4 on
the outdoor unit control board).
(3)
The outdoor unit and the auxiliary unit
(OS) that is connected to the same system
are not properly connected.
Confirm that the TB3 on the OC and OS are
properly connected.
Capacity Total
Model
500 model
650
250 model
SW5
ON
ON OFF OFF
1 2 3 4
Model
Summary of Contents for City Multi PFAV-P500VMH-E
Page 1: ......
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 37: ... 28 ...
Page 39: ... 30 ...
Page 49: ... 40 ...
Page 55: ... 46 ...
Page 59: ... 50 ...
Page 61: ... 52 ...
Page 65: ... 56 ...
Page 67: ... 58 ...
Page 73: ... 64 ...
Page 75: ... 66 ...
Page 95: ... 86 ...
Page 107: ... 98 ...
Page 195: ... X Troubleshooting 186 HWE07150 GB ...
Page 197: ... 188 ...
Page 242: ......