VII
Refrigerant Circuit ]
- 62 -
HWE07150
GB
Linear
expan-
sion
valve
LEV1
(SC control)
Adjusts the amount of bypass flow
from the liquid pipe on the outdoor
unit during cooling
DC12V
Opening of a valve driven by a
stepping motor 0-480 pulses
(direct driven type)
Same as in-
door LEV
The resistance
value differs
from that of the
indoor LEV.
(Refer to the
section "LEV
Troubleshooti
ng."(page 166
))
LEV2a
LEV2b
(Refrigerant
flow adjust-
ment)
Adjusts refrigerant flow during
heating
DC12V
Opening of a valve driven by a
stepping motor 1400 pulses
Same as in-
door LEV
Heater
CH11
Heats the refrigerant in the com-
pressor
Cord heater AC230V
1511 ohm 35W
Resistance
check
4-way
valve
21S4a
Changeover between heating and
cooling
AC208-230V
Dead: cooling cycle
Live: heating cycle
Continuity
check with a
tester
21S4b 1)
Changeover
between
heating
and cooling
2) Controls outdoor unit heat ex-
changer capacity
AC208-230V
Dead: cooling cycle
Outdoor unit heat exchanger
capacity at 100%
Live: heating cycle
Outdoor unit heat exchanger
capacity at 50%
or heating cycle
Part
name
Symbols
(functions)
Notes
Usage
Specifications
Check method
Summary of Contents for City Multi PFAV-P500VMH-E
Page 1: ......
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 37: ... 28 ...
Page 39: ... 30 ...
Page 49: ... 40 ...
Page 55: ... 46 ...
Page 59: ... 50 ...
Page 61: ... 52 ...
Page 65: ... 56 ...
Page 67: ... 58 ...
Page 73: ... 64 ...
Page 75: ... 66 ...
Page 95: ... 86 ...
Page 107: ... 98 ...
Page 195: ... X Troubleshooting 186 HWE07150 GB ...
Page 197: ... 188 ...
Page 242: ......